Stands for: Uninterruptible power supply
Uninterruptible power supply (UPS): a battery-backed unit that keeps equipment running through a utility outage until generators take the load or the power returns.
A UPS buys minutes or hours, not days, and operators' reports show the handover as the weak point: in June 2012 an AWS data centre's generators failed to stabilize and its UPSs ran out seven minutes after the second utility failure. Brazilians call it a nobreak. Regulators set minimum runtimes for some services: the US rules for emergency-call central offices require 24 or 72 hours of backup power at full load.
What it does. A UPS sits between the utility feed and the equipment, carrying the load from its batteries when the utility fails and until a generator is online or the utility returns. How it fails in practice. AWS reported that on 29 June 2012 the generators of one data centre each failed to provide stable voltage, so servers ran on UPS power; after the utility failed again at 7:57 pm, the UPSs were depleted and servers began losing power at 8:04 pm. The FCC's report on the same storm found a central office running on batteries for about six hours after two generators that had to run in tandem failed, and monitoring equipment on a UPS that lasted only thirty minutes, so the operator lost sight of its network before the office itself failed. Google's Paris incident of April 2023 began when cooling water leaked into a UPS room and caused a fire. What rules require. Under 47 CFR 9.19, IP elements of emergency-call networks need an uninterruptible and continuous power supply with switchover to geographically diverse backup facilities, and legacy central offices need 24 or 72 hours of backup power at full office load. Design point. Size and test the UPS against the generator handover actually observed, and give monitoring and management equipment at least the runtime of the network it watches.
Also known as: uninterruptible power supply, nobreak, battery backup
Sources
- Amazon Web Services, Summary of the AWS Service Event in the US East Region, 2 July 2012 (read 2026-11-16): generators failed to provide stable voltage, servers ran on UPS power, UPS systems depleted and servers lost power at 8:04 pm PDT after the second utility failure at 7:57 pm; changes to generator stabilization time, power quality tolerances and staffing
- FCC Public Safety and Homeland Security Bureau, Impact of the June 2012 Derecho on Communications Networks and Services, January 2013 (read 2026-11-16): a central office on batteries for about six hours after two tandem generators failed; monitoring equipment on a UPS that lasts only thirty minutes
- Google Cloud, Multiple Google Cloud services in the europe-west9-a zone are impacted, Paris, 25 April 2023 (read 2026-11-16): a cooling water leak entered an uninterruptible power supply (UPS) room and led to a fire and a power shutdown of the whole building
- United States, Code of Federal Regulations, title 47, section 9.19, eCFR current text (read 2026-11-16): IP 911 elements achieve operational integrity with an uninterruptible and continuous power supply and automatic switchover to geographically diverse backup facilities; legacy central offices need 24 or 72 hours of backup power at full office load