Two nights, one mechanism

On the night of 11 to 12 October 2026, the refrigerated aisles of hundreds of French supermarkets went into defrost and stayed there. By morning, freezers that should have been holding food at well below zero were warm, some far warmer than room temperature, and whole aisles of fresh and frozen products had to be thrown away. On 13 October, France's Finance Minister, Roland Lescure, told Parliament that about 700 of the country's 10,000 supermarkets had been affected, as the Associated Press (AP) reported him.

Three weeks later it happened again. On the night of 1 to 2 November, as Euronews and the BBC reported this morning, fridges and freezers warmed overnight in supermarkets in Belgium, Luxembourg, the Netherlands, Sweden, Finland, Estonia and Ireland. A Belgian refrigeration installer told the Belga news agency that the evaporators had been switched to defrost mode, which he said was the same mechanism as in France.

The obvious question is how anyone can switch a supermarket freezer from the internet. The short answer is that the freezer was never the target. The target is the small computer that runs the whole refrigeration plant of a store, a supervisory controller with a web interface, and in a great many stores that interface was reachable from the internet so that a contractor could look after it remotely. That is an Internet of Things (IoT) story and an operational technology (OT) story at the same time, and it is the same story that sits under almost every notorious IoT hack of the past fifteen years.

Everything below comes from the documents of the parties themselves, the French government's computer emergency response team, the manufacturers, the researchers, regulators and courts, and, where only the press has it, from the press, labelled as such. Every source was read on 2 November 2026 and is listed at the end.

What was attacked: the store's refrigeration supervisor

A supermarket's display cases, cold rooms and freezers each have a small controller of their own, which keeps a setpoint and runs the defrost cycles that stop ice building up on the evaporator coils. Above them sits a system manager that coordinates all of them. Claroty's Team82, which published research on one of these platforms, the Danfoss AK-SM 800A, on 9 August, describes it as "a centralized system manager responsible for coordinating refrigeration controllers throughout an installation", with a web interface from which an operator monitors and configures the whole refrigeration environment. Team82 also says why the interface is there: technicians administer these systems remotely, which saves a trip to every installation. The exposed consoles it found suggested, in its words, "that administrators had exposed the web console for remote management".

That is the detail a network person should hold on to. In France the remote link is the refrigeration contractor's, the prestataire frigoriste, not the store IT department's: the alert from CERT-FR, the computer emergency response team of the national cybersecurity agency ANSSI (Agence nationale de la sécurité des systèmes d'information), speaks of the data sent over the internet to that contractor and of filtering on the contractors' source addresses, and even tells owners to check their insurance contract before cutting that feed. Dominique Schelcher, the chief executive of Coopérative U, put the same point in commercial terms on RTL radio, as the Guardian reported: "Our supermarkets are not customers of Danfoss." The controllers are bought, installed and maintained through a contractor, and many of the people who run the store never see them.

Defrost is the clever part of the attack, and it is clever only in the sense that it is ordinary. A refrigeration controller is supposed to defrost. CERT-FR's alert asks owners to check their whole configuration, "in particular the defrost ranges" (our translation here and below). Press accounts add the rest: BFM TV, as AP relayed it, reported a continuous defrost cycle with temperatures set as high as 50°C, and the Guardian reported that initial investigations suggested the alarms had been disabled, or the defrost programme extended, so that nothing went off until the first employee opened a freezer in the morning.

What the authorities and the manufacturers said

CERT-FR published alert CERTFR-2026-ALE-012 on 12 October and revised it twice: on 13 October to add other targeted equipment, and on 16 October to update its recommendations. As read this morning, it lists the Danfoss AK-SM and AK-SC series and Copeland and Dixell xweb, and says CERT-FR is aware of "numerous compromises" of those remote controllers, that exposing a management interface on the internet "is contrary to good practice", and that attack campaigns against these devices are "probably still under way". The alert names no vulnerability and no actor, and its status on CERT-FR's list is still Alerte en cours (alert ongoing).

Its instructions are the most useful text published about this event, and they are network instructions. Remove the internet exposure of the affected units and of every unit reachable on a public IP address. Restore access only through a secure virtual private network () or a protected network. In an emergency, filter on the contractors' source addresses at a firewall, but do not treat that as lasting. Update the where there is one, set Danfoss equipment's security level to Strict, and make sure default passwords have been changed. And one warning I would print and pin on the wall of every OT team: for an end-of-life device with no security fix, a factory reset removes what the attacker left behind, but "the equipment will remain vulnerable and will certainly be compromised again".

Danfoss gave its account to the trade publication Cooling Post on 12 October. Most of the affected units were legacy products, or current products running outdated firmware: the AK-SM800, declared end of life in 2021, and the AK-SC355, phased out in 2016, neither of which receives software or security updates any more; the current AK-SM800A units that were hit were running outdated firmware. Danfoss said it was working with affected customers on "firmware updates where available, stronger network protections and removing direct internet exposure where applicable". AP quoted the company the same week: it "has long advised customers to keep supported systems updated with the latest firmware, as well as to operate behind a firewall". Danfoss's own security advisories page, read this morning, carries no advisory about the attack; its latest entry, of 18 September, concerns another product line. (Update, 23 November 2026: on 20 November Danfoss published two advisories on these controllers; neither says it was the way in. See the next section.)

Copeland, which owns the Dixell brand, published a product bulletin whose French version, dated 14 October and completed by Dixell France, is the document CERT-FR links from its alert. It acknowledges a vulnerability in a generation of XWEB EVO controllers that is no longer sold and has reached end of life, tells customers to remove every XWEB EVO from the public internet at once, with no port forwarding, no (demilitarized zone) and no direct public IP address, to look for suspicious activity from the local network and to restore the units, and to plan a migration to XWEB PRO, which "must not be exposed to the Internet" either. Its further advice reads like a segmentation lesson, and I come back to it below.

The retailers, as reported: Groupement Les Mousquetaires said 300 of its Intermarché and Netto stores were affected, and Coopérative U's chief executive said 80 of its 2,000, according to AP; the Guardian names Carrefour, Leclerc and Monoprix among the others, and quotes Intermarché's chief executive, Thierry Cotillard, putting the losses at possibly "tens of millions of euros". The Paris prosecutor's office said on 13 October that its cybercrime unit was investigating the attack, including the extent of the damage from spoiled food and reported fires, according to AP. Nobody has claimed it, and no authority has named anyone.

Update, 5 November 2026: after the second wave, two pro-Russian groups, NoName057(16) and Z-Pentest, claimed responsibility on Telegram, as RetailDetail reported on 5 November; the channels have since disappeared and, in that report's words, there is no independent evidence of either group's involvement. No authority has named anyone, and I treat the claim as a claim.

Update, 11 November 2026: on 9 November France attributed the attack of 11 and 12 October to Iran. The foreign ministry's statement names the Shahid Kaveh cyber-offensive unit of the electronic and cyber centre of Iran's Islamic Revolutionary Guard Corps (IRGC), and calls the attack the first cyber-offensive campaign carried out purely for sabotage on French territory. A report published the same day by the C4, the interministerial body that brings together ANSSI, the armed forces' cyber command (COMCYBER), the defence procurement agency (DGA) and the foreign and domestic intelligence services (DGSE and DGSI), sets out the evidence (CERTFR-2026-CTI-009): about 700 retail sites hit, with fires in at least 15 cases; infrastructure used in the same period to reconnoitre Schneider Electric equipment, which the C4 links to the same attack on small French hydroelectric installations; the FOFA scanning tool; the attack relayed by the unit's CyberbanNews outlet from 13 October; and traces of Farsi in the attack infrastructure. The Paris prosecutor's office opened a judicial investigation, aggravated by the aim of serving a foreign power, "in this case Iran", assigned jointly to its anti-cybercrime office (OFAC) and the DGSI. These documents concern the October attack in France; none of them attributes the November wave.

Which flaw? No document names one

It is tempting to write that a known vulnerability went unpatched. The record is more interesting than that, and less tidy.

Danfoss's system managers have a public vulnerability history. In January 2023, researchers from HackDefense reported flaws in the AK-SM 800A through the Dutch Institute for Vulnerability Disclosure (DIVD), which, after Danfoss published its advisory DSA-2023-08-01 in August 2023 (three CVEs, fixed in release 3.3), began notifying the owners of vulnerable internet-facing units in September 2023. Those three CVEs, entries in the Common Vulnerabilities and Exposures list, were the first of several. In March 2025 Danfoss published DSA-2025-03-01, -2025-41450, an authentication bypass in the AK-SM 8xxA series scored 8.2 under the Common Vulnerability Scoring System (), fixed in release 4.2; in August 2025, DSA-2025-08-01, two post-authentication flaws, CVE-2025-41451 (command injection leading to ) and CVE-2025-41452, fixed in 4.3.1. Both 2025 advisories credit Tomer Goldschmidt of Claroty Team82.

Team82's of 9 August 2026 sums up what it found: a hidden "code-of-the-day" authentication mechanism, which it believes was "likely intended for support or maintenance", that could be abused to bypass normal authentication, a command injection that led to remote code execution, and a way for an authenticated user to inject web server configuration. Before looking at the firmware, Team82 counted exposed management interfaces with internet-wide scanning services and reports 2,765 AK-SM 800A devices exposed according to Censys. The Cybersecurity and Infrastructure Security Agency (CISA) published a separate advisory in February 2026, ICSA-26-057-10, for 23 vulnerabilities in Copeland XWEB and XWEB Pro, also reported by Team82, with fixes for XWEB Pro.

Team82's account of the code of the day, CVE-2025-41450, is short and worth knowing in outline. Instead of checking the configured administrator password, the web application accepted a specially crafted authentication request carrying a generated "code of the day", which it checked against a password the device generated internally from its current date and time. Team82 says it fully reconstructed the routine that produces the daily code, so that "anyone capable of reproducing the algorithm could generate valid authentication credentials without knowing the administrator's password", and that a login through this path gave "a fully authenticated administrative session". For an owner, the point is that a credential nobody at the site had chosen opened the administrative interface. Team82's advice is firmware R4.3.1 or later and management interfaces kept off the internet; Danfoss had fixed the bypass itself in release 4.2, in March 2025.

Now put those next to what the parties said in October. CERT-FR's alert lists no CVE. Danfoss says the majority of the units hit were either legacy AK-SM800 and AK-SC355 systems, which are not the AK-SM 800A of the advisories above and get no updates, or current AK-SM800A units on outdated firmware, without saying which release. Copeland says its affected generation is end of life, and does not say which vulnerability. So no first-party document I read says which flaw was used, or whether any flaw beyond reachable, unprotected logins was needed. The one movement in the records since the attack is CISA's: entries dated 19 October in each of the three 2025 Danfoss CVE records, under its Stakeholder-Specific Vulnerability Categorization (SSVC), give the exploitation status as "poc", a public proof of concept. None of them is in CISA's catalogue of known exploited vulnerabilities (version 2026.11.04, read on 5 November 2026).

Update, 5 November 2026: two first-party documents published since still name no flaw. The Centre for Cybersecurity Belgium (CCB), in its update of 3 November, says attackers are "actively taking advantage of unpatched firmware, internet-exposed web interfaces, and unchanged default vendor credentials" on Danfoss AK-SC and AK-SM, Dixell xweb and Copeland xweb devices. A joint factsheet published on 5 November by CISA, the FBI and the US Departments of Health and Human Services, Agriculture and Transportation says actors target refrigeration controllers in retail grocery and cold storage and may use authentication bypass, arbitrary code injection or weak configurations on controllers that are unpatched or reachable from the internet; it names no vendor and no CVE.

Update, 11 November 2026: the French authorities have still named no flaw, but they have said what the attack relied on. ANSSI's director general, Vincent Strubel, told the Senate's foreign affairs committee on 21 October, as Public Sénat reported, that refrigeration equipment exposed directly on the internet and administered without particular protection, and weak passwords, were among the basic security failures behind it; the C4 report of 9 November names no vulnerability. Copeland's product security page carries an undated statement that "certain XWEB monitoring solutions are impacted by the reported cybersecurity vulnerability", without saying which.

Update, 11 November 2026: on 3 November CISA added a reference tagged "exploit", to a public repository I have not opened, to the record of CVE-2025-41452. Its SSVC entry still reads proof of concept, not active exploitation, and no authority has tied that flaw to the attacks. Update, 24 November 2026: the same reference tagged "exploit" is in CISA's section of all three 2025 Danfoss records, CVE-2025-41450 and CVE-2025-41451 since 19 October and CVE-2025-41452 since 3 November; CISA's SSVC entries for all three still read proof of concept, and no authority has tied any of these flaws to the attacks.

Update, 23 November 2026: Danfoss has now published two advisories on these controllers, both dated 20 November. DSA-2026-12-01 describes a stack-based buffer overflow in an unauthenticated Common Gateway Interface () handler of the AK-SM 8xxA series, version 5.4.0 and earlier, which includes 5.4.0, the latest package on Danfoss's software page when I read it on 11 November; it is to be fixed in the upcoming 5.5.x software, after which, Danfoss says, customers will no longer be able to turn Strict mode off. DSA-2026-12-02, "Exploitation of Weak or Known Passwords in Danfoss AK-SC 355 and AK-SM 800 Series", covers those two legacy lines, all versions, for which Danfoss recommends removing internet exposure and moving to the AK-SM 800A series. Neither advisory says it was the way in for the attacks, so no document from the parties names the flaw yet. When read on 23 November, Danfoss's table gave CVE-2026-127057 to the buffer overflow, but the CVE record of that number, published by Danfoss on 20 November, describes the default and known passwords of the AK-SC 355 and AK-SM 800, with a CVSS 4.0 score of 9.9 and a CISA SSVC entry of exploitation none, automatable yes, technical impact total. Update, 25 November 2026: the mismatch is resolved. Danfoss's table and DSA-2026-12-01 now give the buffer overflow its own identifier, CVE-2026-129713, and keep CVE-2026-127057 for the passwords of DSA-2026-12-02; the record of CVE-2026-129713, published by Danfoss on 20 November, scores it 9.3 under CVSS 4.0 and has no CISA entry yet, and the fix is still announced for the upcoming 5.5.x software (read 2026-11-25, 06:35). CISA's catalogue (version 2026.11.23) lists no Danfoss, Copeland or Dixell flaw. Until 5.5.x ships, Danfoss's own mitigations for the AK-SM 8xxA are no exposure on a public IP address, remote access only through a secure VPN or a protected network, Strict mode and strong passwords.

Update, 24 November 2026: another first-party document bears on the same controllers. The Dutch security firm Midnight Blue reported in November that its researcher Carlo Meijer found six pre-authentication remote code execution flaws, stack-based buffer overflows, in the AK-SM800A, affecting every firmware version up to and including 5.3.2, the latest when it wrote; the CVE numbers were pending, and the technical details are withheld while it works with Danfoss on coordinated disclosure. Midnight Blue does not say these flaws were used in the attacks: citing SentinelOne, it says attribution remains open. Neither Midnight Blue nor Danfoss says whether DSA-2026-12-01, the buffer overflow of 20 November, is one of the six. Midnight Blue's advice is the one that runs through this post: reduce exposure, with a VPN, a private access point name (APN) on the mobile network or a strict allow list of IP addresses, rather than rely on piecemeal patching.

My assessment, labelled as such: the detail of which bug matters less here than the shape. The fleets that were hit combined three things, a management interface reachable from the internet, a device that its maker no longer fixes or a fixed device that nobody had updated, and an access model built for a contractor's convenience. Any one of those can be survived. All three together is what CERT-FR's warning about end-of-life devices describes.

Timeline

DateEventSource
2016 and 2021Danfoss phases out the AK-SC355 (2016) and declares the AK-SM800 end of life (2021)Danfoss, via Cooling Post
18 January 2023HackDefense researchers report AK-SM 800A flaws through DIVDDIVD-2023-00025
21 August 2023Danfoss DSA-2023-08-01: three CVEs in the AK-SM 800A, fixed in release 3.3Danfoss
27 September 2023DIVD starts notifying owners of vulnerable internet-facing unitsDIVD-2023-00025
24 March 2025DSA-2025-03-01: CVE-2025-41450, authentication bypass, fixed in 4.2Danfoss
1 August 2025DSA-2025-08-01: CVE-2025-41451 and CVE-2025-41452, fixed in 4.3.1Danfoss
26 February 2026CISA ICSA-26-057-10: 23 CVEs in Copeland XWEB and XWEB ProCISA
9 August 2026Claroty Team82 publishes its AK-SM 800A research; 2,765 exposed devices in CensysClaroty
From 26 August 2026Refrigeration outages at several US military commissaries; military investigators open casesMilitary Times; Stars and Stripes; Newsweek
Night of 11 to 12 October 2026Refrigeration in hundreds of French supermarkets forced into defrost overnightAP; Guardian; Cooling Post
12 October 2026CERT-FR alert CERTFR-2026-ALE-012; Danfoss's statementCERT-FR; Cooling Post
13 October 2026CERT-FR adds other targeted equipment; the Finance Minister gives about 700 of 10,000 supermarkets; the Paris prosecutor's cybercrime unit is investigating; Copeland speaks of an end-of-life generationCERT-FR; AP
14 October 2026Copeland Controls bulletin on XWEB EVOCopeland
16 October 2026CERT-FR updates its recommendationsCERT-FR
19 October 2026CISA's entry in the three 2025 Danfoss CVE records: exploitation "poc"CVE records
Night of 1 to 2 November 2026Fridges and freezers warmed overnight in stores in seven more European countries (nine, as later reported); Belgian federal prosecutor opens an investigationEuronews; BBC
3 November 2026The Centre for Cybersecurity Belgium updates its warning of 13 October for the second waveCCB
5 November 2026Two pro-Russian groups' claim of responsibility is reported; CISA, the FBI and three US departments publish a joint factsheet on attacks on refrigeration and cold-chain systemsRetailDetail; CISA
9 November 2026France attributes the October attack to the IRGC's Shahid Kaveh unit; C4 report CERTFR-2026-CTI-009; the Paris prosecutor opens a judicial investigationFrench foreign ministry; CERT-FR; Paris prosecutor
20 November 2026Danfoss publishes DSA-2026-12-01 (AK-SM 8xxA, buffer overflow, fix in 5.5.x, CVE-2026-129713) and DSA-2026-12-02 (legacy AK-SC 355 and AK-SM 800, weak or known passwords, CVE-2026-127057), and the CVE records of bothDanfoss; CVE records

The second wave, as reported this morning

This part is still moving, and everything in it comes from the press of today, 2 November, relaying what the companies and agencies said. Euronews counts about 75 affected stores in Belgium, from figures in Le Soir: around 40 Delhaize Proxy supermarkets, 15 Carrefour Shop & Go, 15 Intermarché and five Spar Q8 service-station shops, plus a butchery group and the IKEA store at Mons. Carrefour Belgium said 15 of its 700 stores were affected, none of them hypermarkets, and its spokesman said "It's a cyberattack, there is no other reason". The Belgian federal prosecutor's office has opened an investigation, and the Centre for Cybersecurity Belgium (CCB) said it was aware of an incident but had no further information.

Outside Belgium, the BBC reports that ICA said a "small number of ICA stores operating outside ICA's central network" were affected in Sweden, and that Coop counted seven of its 800 Swedish stores; that Musgrave, which owns SuperValu, confirmed to the Irish Times a "cyber incident" at 13 Irish stores, limited to a "specific model" of refrigerator; that Danfoss told the Dutch broadcaster NOS that the cooling systems of at least 17 companies in the Netherlands were attacked overnight, affecting butchers' shops and small neighbourhood stores; that a Selver store in Estonia was affected; and that refrigerator malfunctions were detected at some of Kesko's K-stores in Finland. Danfoss told the Belgian broadcaster VTM, as Euronews relayed, that the vulnerability lies primarily in outdated software and that it had urged customers to move to its newer software. The UK's National Cyber Security Centre (NCSC) said it was working with partners to "fully understand details of an incident"; no UK incident has been reported.

Two sentences from that coverage are worth a network engineer's attention. ICA's says the stores that were hit sat outside its central network; my reading is that they sat outside whatever controls that network applies. And Stephan Moelans, chief executive of Sabcobel, the installer that runs Delhaize's refrigeration, told Belga that his company had been working since the French attack to protect customers against this vulnerability, that a software update alone is not enough and physical modifications are needed, which takes investment, and that "the simplest solution is to manage the fridges over a secure internet connection. Most of our customers switched to that after the attack in France." Three weeks after a national alert, the change most of his customers had made is, as I read it, the one CERT-FR's alert recommends: take the controller off the open internet and reach it through a protected path.

Update, 5 November 2026: the count of countries grew after this was written. Grupo Mosqueteiros told the Portuguese broadcaster RTP that seven Intermarché stores in Portugal were affected by an attack that "is believed to have targeted an external service provider", an outside contractor managing the refrigeration, and AFP, as The Hacker News relayed, reported affected Coop stores in Sicily. The two waves now span ten countries in the press reports, Finland among them, where Kesko said the cause was still under investigation. The CCB, which had warned Belgian organizations on 13 October, the day after CERT-FR's alert, published an update on 3 November naming Belgium, Luxembourg, the Netherlands, Sweden, Ireland and Estonia and describing defrost cycles of up to +50°C overnight. Sweden's National Cyber Security Centre said on 2 November that it was in contact with affected businesses and with its Nordic and European counterparts, and asked organizations to check which OT devices are connected to the internet.

Update, 11 November 2026: the European Union has since spoken with one voice. A joint statement of 4 November from the European Commission, ENISA (the European Union Agency for Cybersecurity), Europol's European Cybercrime Centre (EC3), the network of the member states' computer security incident response teams (the CSIRTs Network) and EU-CyCLONe, the network of national cyber crisis authorities, says that "since 11 October 2026, several commercial refrigeration systems and similar devices have been impacted by cybersecurity incidents in a number of EU Member States", with a new wave on 1 to 2 November, and advises organizations "to take immediate action to mitigate exposure in the affected systems". It also reminds manufacturers that since 11 September 2026 they must report severe incidents and actively exploited vulnerabilities through the Cyber Resilience Act's single reporting platform. The CSIRTs Network's own advisory, CNW-2026-05 of 3 November, gives the CVE as "-" and, as read on 11 November, links the alerts of twelve national teams, among them CERT-FR, the Irish and Italian national centres and Germany's Federal Office for Information Security (BSI). The Dutch National Cyber Security Centre (NCSC-NL), writing on 2 November, says how attackers get in: through vulnerabilities in refrigeration systems connected to the internet, among other things by abusing "poor and default passwords".

A transatlantic footnote: the commissaries

In late August, before France, several US military commissaries, the grocery stores on bases, reported refrigeration failures within days of each other. Fort Huachuca's own post, as Military Times quoted it, said "ALL freezers went into defrost mode". A defence official confirmed to Military Times "a possible refrigeration disruption at some Defense Commissary Agency commissaries", and Stars and Stripes reported that the Army Criminal Investigation Division's (CID) Cyber Field Office and the Air Force Office of Special Investigations had opened investigations. In late October, a CID spokesman told Newsweek the division was working with the Defense Criminal Investigative Service "and French law enforcement in understanding the refrigeration outages in Europe". No official has said publicly what caused the American outages, which equipment was involved, or whether they are connected to Europe, and I do not assume they are.

Update, 5 November 2026: CISA, the FBI and three US departments published a joint factsheet on 5 November about malicious activity targeting industrial refrigeration and cold-chain monitoring systems "globally". It names no actor, no vendor and no incident, and does not mention the commissaries, so the question above stays open.

Update, 11 November 2026: Stars and Stripes reported on 4 November that, two months on, the Pentagon was still investigating the August outages and had not named a cause; a Pentagon official said Defense Cyber Defense Command was working with interagency and law enforcement partners, and Army CID was also working with French law enforcement on the outages in France. The same report says four commissaries in Germany and England had refrigeration outages in late September, which the Defense Commissary Agency put down to equipment failures and delays in obtaining replacement parts. No official document links the commissaries to the European attacks.

The same lesson, a decade of times

None of this is new in kind. What is new is the scale and that the payload was food. Here are the cases I would put in front of a class, each from the documents of the people who handled it, and each for the one thing it teaches.

YearIncidentEntry point, per the recordWhat it teaches
2010Industrial control systems; code modified on programmable logic controllersPhysical processes can be attacked through their controllers
2013TargetA refrigeration contractor's network credentialsThe contractor's access is part of your perimeter
2015Jeep CherokeeThe infotainment unit, reachable over the cellular networkA block in the 's network closed the remote path before owners patched
2016Cameras, routers and video recorders with factory loginsYou cannot patch a default
2017Abbott pacemakersRadio-frequency authentication that could be bypassedSome updates carry their own risk and need a human decision
2018Casino fish tank (an anecdote, told in 2018)A connected aquarium thermometer, as told by Darktrace's chief executiveEvery connected thing on a flat network is a door
2021Oldsmar water plantRemote desktop software on an outdated operating system, as first reportedIndependent physical safeguards, and how first accounts can change
2024Verkada (settlement)The company's alleged failures in access management and data protectionCloud-managed means the vendor's security is yours
2024Integrity Tech botnet (Flax Typhoon)Over 260,000 routers, firewalls, storage and IoT devices, many likely still supportedBotnets do not need end-of-life devices, only exposed ones
2025BADBOX 2.0Devices compromised before purchase or during set-upThe supply chain can deliver the compromise in the box

Stuxnet, briefly, because it is industrial control rather than IoT: Symantec's dossier of February 2011 describes a threat "targeting a specific industrial control system likely in Iran" that modified code on Siemens programmable logic controllers to make them operate "most likely out of their specified boundaries". It belongs here as the proof, from 2010, that the controller is the target.

Target, 2013, is the case closest to this month's in its anatomy. The US Senate Commerce Committee's majority staff report of 26 March 2014 says the attackers "reportedly first gained access to Target's system by stealing credentials from an HVAC and refrigeration company, Fazio Mechanical Services" (HVAC being heating, ventilation and air conditioning), a contractor the report describes as specializing in refrigeration for supermarkets, which had remote access to Target's network for billing and project management. The report's findings include that Target "gave network access to a third-party vendor" whose security was weak, and that the attackers then appear to have moved to the areas storing consumer data, "suggesting that Target failed to properly isolate its most sensitive network assets". Thirteen years apart, the same kind of company holds the same kind of key.

The Jeep Cherokee, 2015. Charlie Miller and Chris Valasek's paper of 10 August 2015, "Remote Exploitation of an Unaltered Passenger Vehicle", records that they disclosed to Fiat Chrysler from October 2014, that Chrysler released a patch on 16 July 2015, and that on 24 July the cellular carrier's network was reconfigured to block the traffic and Chrysler recalled 1.4 million vehicles. The National Highway Traffic Safety Administration (NHTSA) recall record, 15V-461, counts 1,416,903 vehicles with radios whose software "can allow third-party access to certain networked vehicle control systems", and states that Chrysler had the wireless provider close the open cellular connection to the vehicle, adding that the measure may not have reached every vehicle. That is the detail I would put in front of a class: one change in the carrier's network closed the long-distance path to unpatched cars before most owners could have installed the update, and the researchers note that what remained needed an attacker close to the vehicle.

Mirai, 2016, has its own article, Mirai: the botnet that logged in, so only two records here. CISA's alert TA16-288A of October 2016 says the bot used "a short list of 62 common default usernames and passwords" to find its devices. And the US Department of Justice announced on 13 December 2017 that the three authors had pleaded guilty in the District of Alaska on 8 December, that the botnet targeted "wireless cameras, routers, and digital video recorders", that at its peak it held "hundreds of thousands of compromised devices", and that after the source code was posted "other criminal actors have used Mirai variants". The distributed denial-of-service family history places the Dyn attack of October 2016 in that lineage.

Abbott's pacemakers, 2017. CISA's advisory ICSMA-17-241-01 of 29 August 2017 describes pacemakers whose radio-frequency authentication "can be compromised or bypassed, which may allow a nearby attacker to issue unauthorized commands". The fix was firmware, applied to an implanted device through a programmer in a clinic, and the advisory asks healthcare providers to weigh "the potential risk of a cybersecurity attack along with the risk of performing a firmware update". It is the cleanest example I know that patching is a decision with its own risk, which is exactly the decision a supermarket faces when an update needs a technician on site.

The casino fish tank is an anecdote, and I tell it as one. In April 2018, Darktrace's chief executive Nicole Eagan told the Wall Street Journal's CEO Council conference, as Business Insider reported, that in one case her company worked on, attackers got into a casino through a thermometer in a lobby aquarium, "found the high-roller database and then pulled that back across the network, out the thermostat, and up to the cloud". The casino is unnamed, and I know of no public technical record of it. It survives in every IoT talk because it is the flat-network lesson in one sentence.

Oldsmar, 2021, is the one that teaches humility. The advisory that the Federal Bureau of Investigation (FBI), CISA, the Environmental Protection Agency and the Multi-State Information Sharing and Analysis Center issued in February 2021, AA21-042A, still reads that on 5 February "unidentified cyber actors obtained unauthorized access" to a water plant's supervisory control and data acquisition (SCADA) system and raised the sodium hydroxide dose, that plant personnel noticed and corrected it at once, and that the access likely came through poor password security, an outdated operating system and possibly desktop-sharing software. The same advisory, as published today, also says the FBI "was not able to confirm that this incident was initiated by a targeted cyber intrusion", and in 2023 the city manager at the time, Al Braithwaite, said it was a "nonevent" likely caused by employee error, as the Tampa Bay Times reported. Two lessons, then: the advisory's own best recommendation, independent physical safety systems that stop a dangerous dose whatever the software says; and that the first account of an OT incident is a hypothesis.

Verkada, settled in 2024. The Department of Justice announced on 4 September 2024 that Verkada, a cloud-based security camera company, would pay a $2.95 million civil penalty, and set up a comprehensive information security programme with regular third-party assessments, to resolve allegations, brought with the Federal Trade Commission (FTC), that it had failed to implement reasonable security, such as appropriate access management, and that this exposed customers' camera footage, from places such as hospitals and schools, to unauthorized access. When the device is managed from the vendor's cloud, the vendor's access controls are part of your camera.

The Integrity Tech botnet, 2024, and BADBOX 2.0, 2025, are the current shape. The joint advisory of 18 September 2024 from the FBI, the Cyber National Mission Force and the National Security Agency describes a botnet controlled by Integrity Technology Group, a company based in the People's Republic of China, whose control addresses, the FBI says, were also used in intrusions consistent with the group known publicly as Flax Typhoon: over 260,000 routers, firewalls, network storage and IoT devices as of June 2024, recruited with malware of the Mirai family. It adds a sentence that should worry anyone who thinks only old kit is at risk: "many of the compromised devices ... are likely still supported by their respective vendors". The FBI's public service announcement of 5 June 2025 on BADBOX 2.0 describes "millions of infected devices", streaming boxes, projectors, picture frames, compromised either before purchase or while downloading apps during set-up. That is the supply chain delivering the attacker's access in the box.

The causes that keep coming back

Read the table again and the same handful of causes appear, in different clothes.

  • Logins that the owner did not choose. Mirai's factory passwords, the hidden "code of the day" Team82 found, the default passwords that CERT-FR tells Danfoss owners to change, and the default password that Marta Rybczyńska, a security researcher quoted by the Guardian, says many of the French freezers appeared to run with.
  • Management interfaces that face the internet. Team82's 2,765 AK-SM 800A interfaces in Censys, the XWEB units that Copeland says must have no port forwarding, no DMZ and no public address, the cellular interface on the Jeep, and CERT-FR's general rule that exposing a management interface on the internet is contrary to good practice.
  • No update path, or no update. The AK-SC355, phased out in 2016, and the AK-SM800, end of life since 2021, get no updates, the XWEB EVO is end of service, and Oldsmar's advisory warns about Windows 7. Equally common is the supported device that nobody updated: Danfoss's AK-SM800A units on old firmware, after fixes published in 2023 and 2025.
  • Access that belongs to someone else. Fazio Mechanical at Target, the frigoristes in France, the refrigeration installers in Belgium, Verkada's cloud. The people who need remote access are not the people who own the network, and their access is often the least watched path in.
  • Flat networks. Target's report says it plainly. The casino anecdote says it memorably. ICA's stores "operating outside ICA's central network" say it from the other side, as I read it: whatever controls the central network had, those stores were not behind them.
  • Alarms that run on the same system as the thing they watch. If the reported detail holds, the French attack disabled the alarms or extended the defrost programme so that they did not trigger, and nobody knew until morning. My assessment: a temperature alarm that the attacker can switch off from the same console is a configuration setting, not a safeguard. Oldsmar's advisory has the better model, an independent safety system.

What changed in law and standards, and what it reaches

The Mirai article tells how regulation became the answer to defaults that no market would fix. Here is where the main texts stand today, from the bodies that publish them.

TextWhat it requiresApplies toStatus, as read on 2 November 2026
UK Product Security and Telecommunications Infrastructure () Act 2022 and its 2023 security requirements regulationsPasswords "unique per product" or "defined by the user"; a published contact for reporting security issues; a published minimum period of security updatesRelevant connectable products for UK consumersIn force since 29 April 2024
ETSI EN 303 645, "Cyber Security for Consumer Internet of Things", from the European Telecommunications Standards InstituteThirteen groups of provisions, starting with "No universal default passwords" and a means to manage vulnerability reportsConsumer IoT devicesVersion 3.1.3, September 2024
EU Radio Equipment Directive delegated regulation (EU) 2022/30Activates the essential requirements of Articles 3(3)(d), (e) and (f), for cybersecurity, personal data protection and privacyCertain categories of radio equipmentIn application since August 2025; repealed with effect from 11 December 2027 by (EU) 2026/339, when the CRA takes over
EU , Regulation (EU) 2024/2847Essential cybersecurity requirements in design and production, vulnerability handling for a declared support period, reporting, CE markingHardware and software "products with digital elements" on the EU marketIn force since 10 December 2024; reporting obligations since 11 September 2026; main obligations from 11 December 2027
US Cyber Trust MarkA voluntary labelWireless consumer IoT productsRules adopted 14 March 2024; the Federal Communications Commission (FCC) says it is "now in the process of standing up" the programme

Two things stand out when a supermarket controller is held against that table. First, most of these texts are consumer texts by their own words: the PSTI Act gives the power to set requirements for products "made available to consumers in the United Kingdom", ETSI EN 303 645 is a standard for consumer IoT, and the FCC's programme is for "wireless consumer IoT products". A refrigeration system manager sold to a contractor for a supermarket is not what they were written for. The CRA is different: the Commission's summary calls it a horizontal framework for hardware and software products made available on the EU market, and its reporting obligations, in the Commission's words, apply to products "including those already placed on the market before 11 December 2027". Danfoss's own disclosure page already cites it.

Second, and this is my assessment, every one of these texts sets its design and update requirements for products as they are placed on the market, with the CRA's reporting duty the one exception that reaches what is already installed, and the controllers hit in October and November were installed years ago, some before any of these texts existed. The CRA's design requirements will shape the controllers sold from December 2027. The AK-SC355 phased out in 2016 will not get a security update from any regulation. For the installed base, the remedy is operational, and it is ours.

What I would do this week

If I ran refrigeration, building management or any other OT in a store, a warehouse or a plant, this is the list, in this order. Most of it comes straight from CERT-FR's alert and Copeland's bulletin; the rest is the network practice I teach, labelled where it is my addition.

  1. Find every controller, by what is reachable, not by what is on the asset register. Ask each contractor, in writing, which devices they reach remotely and how. Then test from outside, the way Copeland's bulletin suggests: from a phone with turned off, type the site's public address into a browser; the controller's login page must not appear. Inside, an OUI lookup on the MAC addresses in the switch tables (the organisationally unique identifier is the manufacturer's prefix) will show you manufacturers you did not know were on the network.
  2. Remove inbound exposure, completely. No port forwarding, no DMZ, no public address, as Copeland puts it; CERT-FR asks for the same of every unit exposed on a public IP address. If the controller has a public IP address today, that is the first change.
  3. Give the contractor a controlled path in. A VPN or a zero trust network access () service that knows who the technician is, uses multi-factor authentication () where it can, and logs each session; the zero trust article covers the options. CERT-FR accepts filtering on the contractor's source addresses only as an emergency measure, and so would I: an address says where a connection came from, not who made it.
  4. Put the controllers on their own segment. A dedicated virtual local area network (), separate from the office, the tills and the guest Wi-Fi, as Copeland's bulletin says, with outbound traffic limited to what the controller needs, its examples being the mail server, DNS, the Network Time Protocol () and the vendor's update server, and everything else blocked. Write the rules as an access control list () and check its first-match behaviour before you deploy it with the ACL first-match evaluator; the CIDR calculator helps with the addressing of the new segment. The segmentation article explains why the hard part is knowing what talks to what.
  5. Change every credential, and keep changing it. Named accounts, no shared ones, the least privilege each person needs, and new passwords after every contractor intervention with a privileged account, all from Copeland's list. On Danfoss AK-SM 800A, update the firmware and set the security level to Strict, as CERT-FR says.
  6. Decide about the end-of-life units, deliberately. The AK-SM800 and the AK-SC355 get no updates, and the XWEB EVO gets no more security fixes (Copeland asks owners to install its last software release in the meantime), and CERT-FR says a reset alone will not keep them safe. Off the internet and segmented is the plan until they are replaced, and the replacement date belongs in a budget.
  7. Give the alarm a second channel. My assessment, building on the Oldsmar advisory's independent safety systems: a temperature probe and alert path that does not depend on the controller an attacker can reconfigure, so that a warm freezer at 2 a.m. wakes someone up.
  8. Read the contracts. CERT-FR's note about insurance is a reminder that the remote feed to the contractor may be a condition of the insurance contract. Who is responsible for the controller's security, who patches it, and who is told when something changes belongs in the maintenance contract, not in an assumption.
Two ways to reach a store's refrigeration controllerTop: the contractor and anyone scanning the internet both reach the store router, which forwards them to the controller's web interface, which drives the cases. Bottom: anyone scanning finds no inbound path; the contractor comes in through a VPN or ZTNA gateway with a named account and a session log, into a dedicated VLAN that holds the controller and allows only the outbound traffic it needs; an independent temperature alarm sits beside the cases.Exposed, as CERT-FR's alert describesContractor'stechnicianAnyone scanningthe internetInternetStore router: port forward, DMZ or public addressRefrigeration controllerweb interface reachable by anyoneCases and cold rooms: setpoints, defrost, alarmsAs CERT-FR and Copeland recommendContractor'stechnicianAnyone scanningthe internetno inbound path:no port forwarding,no DMZ, no public addressVPN or ZTNA gatewaynamed account, MFA,session logDedicated VLAN for the controllersseparate from office, tills and guest Wi-FiRefrigeration controllercurrent firmware, Strict mode, no default passwordsoutbound only: mail, DNS, NTP, vendor updatesCases and cold roomsIndependent temperature alarmnot raised through the controller (my assessment)
Top: the exposure CERT-FR's alert describes, a management interface reachable from the internet. Bottom: the path its recommendations and Copeland's bulletin describe, with no inbound exposure, access only through a VPN or protected network, a dedicated VLAN with outbound traffic limited, and, for Danfoss equipment, current firmware, Strict mode and changed default passwords. The independent alarm is my assessment, after the safety-system advice in CISA's Oldsmar advisory.

What I take from it

I wrote last week about PHP2Shell and the layer nobody thinks they own. A supermarket's refrigeration controller is that layer in its purest form. IT does not buy it, facilities does not configure it, the contractor maintains it under a service contract, and the manufacturer stopped fixing it years ago. Everyone is reasonable, and the freezer faces the internet.

Thirty years in this industry have taught me that the controls that would have stopped the attacks of October and November are not new: know what you own, do not publish management interfaces, give third parties a controlled door instead of an open one, separate what does not need to talk, and do not let the thing you are protecting also be the only thing that raises the alarm. What has changed is the cost of forgetting them. Ten years ago an exposed controller was a risk on a slide. This year it was food in the bins in two waves across ten countries, as reported, losses that Intermarché's chief executive put at possibly tens of millions of euros, and an alert from the French government's response team that is still open.

CVE Watch follows these vulnerabilities, with their scores, exploitation status and fixed versions read from the sources, each with the time it was read: CVE-2025-41450, CVE-2025-41451, CVE-2025-41452.

Sources

All read on 2 November 2026, between 12:21 and 13:15 São Paulo time, except Claroty Team82's write-up, whose server refused automated reads that day; it was read on 5 November 2026 at 12:23, and the post's account of it stands.