# Redundant architectures: how networks survive failure

> Redundancy is a second way to perform a function, paid for in equipment, complexity and testing, and it helps only against failures that cannot reach both ways at once. This article maps the failure domains from a power supply to a cloud region, walks the layers where networks add redundancy (power and paths, layer 2, the first hop, layer 3, stateful devices, application delivery and global load balancing, data and services, operations) with the time each needs to notice a failure, and reads twelve operators' and regulators' reports on outages in which redundancy did not hold. After reading, you can place any redundancy mechanism in its layer and failure domain, estimate how long it takes to fail over, and ask the questions that find a shared fate before an outage does.

Source: https://ronutz.com/en/learn/redundant-architectures-how-networks-survive-failure  
Updated: 2026-11-23  
Related tools: https://ronutz.com/en/tools/vrrp-timer-calculator, https://ronutz.com/en/tools/bfd-timers, https://ronutz.com/en/tools/lacp-hash-and-state-reader, https://ronutz.com/en/tools/stp-election-calculator, https://ronutz.com/en/tools/fortigate-ha-failover-simulator, https://ronutz.com/en/tools/bigip-dns-gslb-simulator, https://ronutz.com/en/tools/change-blast-radius-mapper, https://ronutz.com/en/tools/flow-path-reasoner

---

A network survives a failure only when a second way to do the same job exists, notices that the first one has gone, takes over in time, and was not broken by the same cause. Each of those four conditions has a price and a way to fail, and the published reports on large outages show that the fourth one, the shared cause, is where redundancy most often stops working. This article opens a series of ten. It defines redundancy in the words of the standards, maps the failure domains from a power supply to a cloud region, walks the layers in which networks add redundancy with the time each layer takes to notice a failure, and reads twelve outages through the operators' own post-mortems and regulators' reports. After reading, you can place any redundancy mechanism in its layer and its failure domain, estimate the time a failover takes from its timers, and ask the questions that find a shared fate before an outage does.

## What redundancy is, in the standards' words

The vocabulary that the International Organization for Standardization (ISO), the International Electrotechnical Commission (IEC) and the Institute of Electrical and Electronics Engineers (IEEE) publish together, ISO/IEC/IEEE 24765:2017, defines redundancy, "in fault tolerance", as "the presence of auxiliary components in a system to perform the same or similar functions as other elements for the purpose of preventing or recovering from failures" ([IEEE Computer Society and ISO/IEC JTC 1/SC 7, SEVOCAB, redundancy](https://pascal.computer.org/sev_display/index.action)). The same vocabulary separates the ways of doing it. Active redundancy runs the redundant elements simultaneously; standby redundancy leaves them inoperative until a primary element fails; homogeneous redundancy realizes the same function with identical means, such as two identical processors; and diversity realizes it by different means, such as different processors, storage media, programming languages, algorithms or development teams ([SEVOCAB, redundancy, active redundancy, standby redundancy, homogeneous redundancy, diversity](https://pascal.computer.org/sev_display/index.action)).

The International Telecommunication Union's Telecommunication Standardization Sector (ITU-T) defines what redundancy is for. Recommendation E.800 calls availability the ability of an item "to be in a state to perform a required function at a given instant of time or at any instant of time within a given time interval, assuming that the external resources, if required, are provided", and reliability "The probability that an item can perform a required function under stated conditions for a given time interval" ([ITU-T E.800 (09/2008), sections 3.1.1.5.4 and 3.1.1.5.5](https://www.itu.int/rec/dologin_pub.asp?lang=e&id=T-REC-E.800-200809-I!!PDF-E&type=items)). The clause about external resources matters: an availability figure for a router says nothing about the power feed it assumes.

Transmission engineers name the arrangements by how many spares protect how many working paths. Request for Comments (RFC) 4427 of the Internet Engineering Task Force (IETF) defines 1+1 protection as one working and one protection path with "a permanent bridge", the traffic sent down both and the better copy selected at the far end; 1:N as N working paths sharing one protection path that may carry extra traffic while idle; and M:N as N working paths sharing M protection paths ([RFC 4427, April 2006, sections 6.1 to 6.3](https://www.rfc-editor.org/rfc/rfc4427.txt)). The data-centre shorthand of N+1 and 2N reads the same way, and [the next part of this series](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate) works through what each buys.

The Internet itself began with a deliberate choice about where not to put redundancy. David Clark's account of the design philosophy of the Defense Advanced Research Projects Agency (DARPA) protocols explains that state about a connection could have been replicated inside the network's switching nodes, but the architecture gathered it at the endpoints instead, an approach he called "fate-sharing": "it is acceptable to lose the state information associated with an entity if, at the same time, the entity itself is lost" ([Clark, The Design Philosophy of the DARPA Internet Protocols, SIGCOMM 1988, reprinted 1995](http://ccr.sigcomm.org/archive/1995/jan95/ccr-9501-clark.pdf)). He gave two reasons: fate-sharing protects against any number of intermediate failures where replication protects against fewer than the number of copies, and "fate-sharing is much easier to engineer than replication" (same paper). Stateless routers are the reason a routed core can lose a router and keep every Transmission Control Protocol (TCP) connection that crossed it, and the stateful devices of the later layers are where that property ends.

## What redundancy buys, and what it costs

Google's site reliability engineers describe the cost curve from their own operations: "an incremental improvement in reliability may cost 100x more than the previous increment", paid in redundant machines and in the opportunity cost of engineers building reliability instead of features ([Google, Site Reliability Engineering, chapter 3, Embracing Risk](https://sre.google/sre-book/embracing-risk/)). The same chapter sets a ceiling on what users notice: "a user on a 99% reliable smartphone cannot tell the difference between 99.99% and 99.999% service reliability!", and treats an availability target "as both a minimum and a maximum".

The second cost is complexity. RFC 3439 states the Simplicity Principle, that "complexity is the primary mechanism which impedes efficient scaling", and quotes a warning that applies to every redundancy mechanism: "complexity added for robustness also adds new fragilities, which in turn leads to new and thus spiraling complexities" ([RFC 3439, December 2002, sections 2 and 9](https://www.rfc-editor.org/rfc/rfc3439.txt)). Its Coupling Principle adds that "as things get larger, they often exhibit increased interdependence between components" (section 2.2.2), which is the arithmetic's independence assumption failing at scale.

The measurements agree that redundancy helps and that it helps less than its diagrams suggest:

| Study | What was measured | What redundancy did |
|---|---|---|
| [Gill, Jain and Nagappan, SIGCOMM 2011](https://conferences.sigcomm.org/sigcomm/2011/papers/sigcomm/p350.pdf) | Over a year of network error logs from thousands of devices in a large operator's data centres (two authors from Microsoft Research) | Median traffic carried during a link failure was 93% across the redundancy group against 65% on the failed link, so redundancy is "only 40% effective in reducing the median impact of failure" |
| [Oppenheimer, Ganapathi and Patterson, USITS 2003](https://www.usenix.org/legacy/events/usits03/tech/full_papers/oppenheimer/oppenheimer.pdf) | Failures of three large Internet services | Redundancy masked most hardware, software and network component failures, but "Fully half of the 36 operator errors resulted in service failure" |
| [Meza and others, IMC 2018](https://conferences.sigcomm.org/imc/2018/papers/imc18-final179.pdf) | Seven years of Facebook's data centre network incidents | Most failures that software could not repair involved maintenance, faulty hardware and misconfiguration, with "2× more human errors than hardware errors" |
| [Govindan and others, SIGCOMM 2016](https://research.google/pubs/evolve-or-die-high-availability-design-principles-drawn-from-googles-network-infrastructure/) | Over 100 high-impact failure events in Google's network | Failures were spread across data, control and management planes, and "a large number of failures happen when a network management operation is in progress" |

Gill and his co-authors give the reasons in their own words: bugs in failover mechanisms when it is unclear which link is the backup, redundant components that were not configured correctly, and once "the same configuration error made on both the primary and back up of a network connection because of a typo in the configuration script" ([Gill and others, section 5.1](https://conferences.sigcomm.org/sigcomm/2011/papers/sigcomm/p350.pdf)). That sentence is the whole subject of this series in miniature: two boxes, one mistake.

## Failure domains, from a power supply to a region

A failure domain is the set of things that one fault takes down together. The cloud providers publish theirs. Amazon Web Services (AWS) describes an Availability Zone (AZ) as one or more data centres "with independent and redundant power infrastructure, networking, and connectivity", placed up to 60 miles (about 100 km) from the others "to prevent correlated failures", and designed to avoid "shared fate scenarios such as utility power, water disruption, fiber isolation, earthquakes, fires, tornadoes, or floods"; generators and cooling are not shared, zones are fed from different substations, and deployments to zones in one region are "separated in time to prevent correlated failure" ([AWS, AWS Fault Isolation Boundaries, Availability Zones](https://docs.aws.amazon.com/whitepapers/latest/aws-fault-isolation-boundaries/availability-zones.html)). Microsoft says its zones are "typically separated by several kilometers, and usually are within 100 kilometers of each other" ([Microsoft Learn, What are availability zones?, 11 February 2026](https://learn.microsoft.com/en-us/azure/reliability/availability-zones-overview)). Google tells its customers that resources in different zones reduce the risk of one infrastructure outage taking all of them, and that regions provide "an even higher degree of failure independence" across "different failure domains" ([Google Cloud, Regions and zones, last updated 10 November 2026](https://cloud.google.com/compute/docs/regions-zones)).

The IETF's survivability vocabulary has the same idea for transport networks. RFC 3386 defines a shared risk group as "a set of network elements that are collectively impacted by a specific fault or fault type", including shared conduit, shared fibre cable, shared right of way, shared optical ring and shared office ([RFC 3386, November 2002, section 2.2.2](https://www.rfc-editor.org/rfc/rfc3386.txt)); RFC 4202 turns it into a routing attribute, the shared risk link group (SRLG), with the example that "two fibers in the same conduit would be in the same SRLG" ([RFC 4202, October 2005, section 2.3](https://www.rfc-editor.org/rfc/rfc4202.txt)).

| Failure domain | What one fault takes with it | The redundancy that answers it | Part of this series |
|---|---|---|---|
| Component (power supply, fan, optic, line card) | One device's function | A second component in the same chassis | [Physical and power](https://ronutz.com/en/learn/physical-and-power-redundancy-feeds-paths-and-carriers) |
| Device | Every port and session on it | A second device: a link aggregation peer, a gateway peer, a cluster member | [Layer 2](https://ronutz.com/en/learn/layer-2-redundancy-lag-mlag-and-spanning-tree), [first hop](https://ronutz.com/en/learn/default-gateway-redundancy-vrrpv3-glbp-and-anycast-gateways), [stateful clusters](https://ronutz.com/en/learn/stateful-clusters-active-standby-active-active-and-split-brain) |
| Link and path | Traffic on that fibre, and on every fibre in the same conduit | A diverse path; a routing protocol that reroutes | [Layer 3](https://ronutz.com/en/learn/layer-3-redundancy-ecmp-bfd-and-fast-reroute) |
| Rack and power feed | Everything on one feed or one top-of-rack switch | A second feed, a second rack | [Physical and power](https://ronutz.com/en/learn/physical-and-power-redundancy-feeds-paths-and-carriers) |
| Building, campus, zone | Everything behind one set of generators, cooling or entrance | A second site or zone | [Application delivery and global load balancing](https://ronutz.com/en/learn/adc-and-gslb-redundancy-health-monitors-pools-and-site-failover) |
| Region | Everything in one geography and one control plane | A second region | [Data and services](https://ronutz.com/en/learn/data-and-service-redundancy-replication-quorum-rpo-and-rto) |
| Software version, configuration, operator | Every copy that runs the same code, reads the same file or takes the same command | Staged change, diversity, testing | [Testing redundancy](https://ronutz.com/en/learn/testing-redundancy-failure-drills-chaos-and-the-failover-never-tried) |

The last row is not geographic, and the outage table below shows why it belongs in the list. Google's study of a year of its storage clusters found that 37% of node failures were part of a burst of at least two, that most large bursts were associated with rack-level or multi-rack events, and that "the critical element in models of availability is their ability to account for the frequency and magnitude of correlated failures" ([Ford and others, Availability in Globally Distributed Storage Systems, OSDI 2010, sections 1 and 4](https://www.usenix.org/legacy/event/osdi10/tech/full_papers/Ford.pdf)). The [arithmetic part](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate) puts numbers on that sentence.

## How a failover happens, and how long it takes

RFC 5714 breaks a routed network's recovery into five steps, and the breakdown holds for most redundancy mechanisms: detecting the failure, "of the order of a few milliseconds when it can be detected at the physical layer, up to several tens of seconds when a routing protocol Hello is employed"; the local router reacting; passing the news to other routers, "typically between 10 milliseconds and 100 milliseconds per hop"; recomputing, "typically a few milliseconds for a link state protocol"; and loading the new forwarding tables into hardware, which "may be several hundred milliseconds" ([RFC 5714, January 2010, section 4](https://www.rfc-editor.org/rfc/rfc5714.txt)). The packets sent towards the failed component until detection are "unavoidably lost" (same section).

Detection is the step each layer configures, and its defaults differ by three orders of magnitude:

| Layer | Mechanism | Default or suggested timers | Time to declare the failure | Source |
|---|---|---|---|---|
| Layer 2 | Link Aggregation Control Protocol (LACP), slow rate | One message every 30 s, three missed | 90 s | [Extreme Networks, SLX-OS, LACP timeout](https://documentation.extremenetworks.com/slxos/SW/20xx/l2config/GUID-67DF739B-2115-4055-92BE-D1DB02F72B70.shtml); Linux's default is slow ([Linux kernel, bonding](https://docs.kernel.org/networking/bonding.html)) |
| Layer 2 | LACP, fast rate | One message a second, three missed | 3 s | same pages |
| Layer 2 | Spanning Tree Protocol (STP), IEEE 802.1D | Forward delay 15 s, twice | 30 s of disruption in Cisco's example | [Cisco, Understand Rapid Spanning Tree Protocol (802.1w), updated 9 February 2023](https://www.cisco.com/c/en/us/support/docs/lan-switching/spanning-tree-protocol/24062-146.html) |
| Layer 2 | Rapid Spanning Tree Protocol (RSTP), IEEE 802.1w | Hello 2 s; three missed Bridge Protocol Data Units (BPDUs) | Convergence "sometimes in the order of a few hundred milliseconds" | same page |
| First hop | Virtual Router Redundancy Protocol (VRRP) version 3 | Advertisement every 1 s, Backup priority 100 | 3.6094 s (computed below) | [RFC 9568, April 2024, section 6.1](https://www.rfc-editor.org/rfc/rfc9568.txt) |
| First hop | Hot Standby Router Protocol (HSRP) | Hellotime 3 s recommended; Holdtime at least three times the Hellotime | 9 s or more | [RFC 2281, March 1998, section 5.1](https://www.rfc-editor.org/rfc/rfc2281.txt) |
| Layer 3 | Bidirectional Forwarding Detection (BFD), FRRouting defaults | 300 ms intervals, multiplier 3 | 900 ms | [FRRouting, BFD](https://docs.frrouting.org/en/latest/bfd.html) |
| Layer 3 | BFD, RFC 5880's aggressive example | 16.7 ms, multiplier 3 | 50 ms | [RFC 5880, June 2010, section 7](https://www.rfc-editor.org/rfc/rfc5880.txt) |
| Layer 3 | Open Shortest Path First (OSPF) | Hello 10 s on a local area network (LAN), a sample value, dead interval "say 4" times the hello | 40 s | [RFC 2328, April 1998, appendix C.3](https://www.rfc-editor.org/rfc/rfc2328.txt) |
| Layer 3 | Border Gateway Protocol (BGP) | Suggested HoldTime 90 s, keepalive a third of it | 90 s | [RFC 4271, January 2006, section 10](https://www.rfc-editor.org/rfc/rfc4271.txt) |
| Stateful | FortiGate Clustering Protocol (FGCP) heartbeat | 200 ms between heartbeats by default; 20 lost heartbeats by default (hb-lost-threshold), configurable | 2 × 100 ms × 20 = **4 s** by default | [Fortinet, Technical Tip: Interval between HA heartbeats, updated 7 September 2026](https://community.fortinet.com/fortigate-3/technical-tip-interval-between-ha-heartbeats-97919); [Fortinet, FortiOS 7.6.6 Administration Guide, HA heartbeat interface](https://docs.fortinet.com/document/fortigate/7.6.6/administration-guide/849059/ha-heartbeat-interface) |
| Global | Domain Name System (DNS) answer cached by resolvers | Time to live (TTL) chosen by the zone, 0 to 2,147,483,647 s | Until cached answers expire | [RFC 1035, November 1987, section 3.2.1](https://www.rfc-editor.org/rfc/rfc1035.txt); [RFC 2181, July 1997, section 8](https://www.rfc-editor.org/rfc/rfc2181.txt) |

The VRRP row is computed from RFC 9568's own formulas, `Skew_Time = ((256 - Priority) * Active_Adver_Interval) / 256` and `Active_Down_Interval = (3 * Active_Adver_Interval) + Skew_Time`, in centiseconds: a Backup at priority 100 waits 300 + 60.9375 = 360.9375 centiseconds, which is 3.6094 seconds, inside the RFC's promise of convergence in under 4 seconds by default and under 1/25 of a second when configured for it ([RFC 9568, sections 3 and 6.1](https://www.rfc-editor.org/rfc/rfc9568.txt)). The [VRRP timer calculator](https://ronutz.com/en/tools/vrrp-timer-calculator) and the [BFD timer calculator](https://ronutz.com/en/tools/bfd-timers) do the same arithmetic for any configuration, and the BFD articles explain [why a link can be up and dead](https://ronutz.com/en/learn/bfd-when-a-link-is-up-and-dead) and [how the detection time is negotiated](https://ronutz.com/en/learn/bfd-timers-the-arithmetic-of-detection).

Two readings of the table matter for design. Detection is only the first of RFC 5714's five steps, so a 50 ms BFD session does not make a 50 ms failover if the forwarding table takes hundreds of milliseconds to reload. And every failover spends some of the availability budget: at OSPF's sample timers, twelve failovers a year cost 480 seconds of loss before anything else happens, which the [arithmetic part](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate) turns into nines.

## The layers, in order

Each layer below has a part of its own in this series; the sections here say what fails at that layer, what answers it, how long the answer takes, and which existing articles go deeper.

### Physical and power

Everything above depends on electricity, cooling and glass. The AWS description of its zones lists the shared fates it designs against, from utility power and water to fibre isolation, fire and flood ([AWS, Availability Zones](https://docs.aws.amazon.com/whitepapers/latest/aws-fault-isolation-boundaries/availability-zones.html)). Brazil's telecommunications regulator, the Agência Nacional de Telecomunicações (Anatel), added a title on data centres that form part of telecommunications networks to its conformity assessment regulation in August 2025: the operational procedure is to require, among other things, that they "operate continuously, even in situations of failure, adverse events or disasters" (our translation here and below), and the agency's Board suspended the effects of article 6 of the amending resolution on 3 March 2026 while it re-examines the matter ([Anatel, Resolução nº 715/2019, Title VI-A, as amended by Resolução nº 780 of 1 August 2025](https://informacoes.anatel.gov.br/legislacao/resolucoes/2019/1350-resolucao-717)).

The management network belongs to this layer too, because it is how people reach the equipment when everything else is down. Meta's engineers found in October 2021 that "out-of-band network access was down" and had to send engineers to the data centres ([Meta, More details about the October 4 outage, 5 October 2021](https://engineering.fb.com/2021/10/05/networking-traffic/outage-details/)); the Canadian Radio-television and Telecommunications Commission (CRTC) was told that Rogers "had a management network that relied on the Rogers IP core network", the network that had failed ([CRTC, Assessment of Rogers Networks for Resiliency and Reliability Following the 8 July 2022 Outage, Executive Summary, July 2024](https://crtc.gc.ca/eng/publications/reports/xona2024.htm)). Dual power supplies, A and B feeds, uninterruptible power supplies, diverse conduits and carriers, out-of-band management and the facility ratings are the subject of [part 3](https://ronutz.com/en/learn/physical-and-power-redundancy-feeds-paths-and-carriers); the seabed is in [Submarine cables: the internet is a rope on the seabed](https://ronutz.com/en/learn/submarine-cables-and-the-physical-internet).

### Layer 2

Two switches joined by two cables form a loop, and Ethernet has two answers: bundle the cables or block one. A link aggregation group (LAG) lets a media access control (MAC) client treat parallel links "as if it were a single link", and IEEE 802.1AX-2020 extends the idea to a Distributed Resilient Network Interconnect among "one to three nodes in a network and one to three nodes in another" ([IEEE 802.1AX-2020 project page, approved 30 January 2020](https://1.ieee802.org/tsn/802-1ax-rev/)). Spanning tree keeps the loop by blocking a port until it is needed, at the timers in the table above. Ethernet virtual private network (EVPN) multihoming replaces both inside a fabric: RFC 7432 lets a segment attach to several provider edge devices in Single-Active mode, one forwarding per virtual local area network (VLAN), or in All-Active mode, all of them forwarding known unicast traffic ([RFC 7432, February 2015, section 3](https://www.rfc-editor.org/rfc/rfc7432.txt)).

The existing articles cover the mechanisms: [link aggregation and LACP](https://ronutz.com/en/learn/link-aggregation-and-lacp), [spanning tree in one article](https://ronutz.com/en/learn/spanning-tree-in-one-article), [split multi-link trunking (SMLT) and the virtual inter-switch trunk (vIST) on Extreme's fabric edge](https://ronutz.com/en/learn/voss-smlt-and-vist) and [FortiSwitch spanning tree](https://ronutz.com/en/learn/fortiswitch-vlans-stp-ports-and-qos). The [LACP member link and state reader](https://ronutz.com/en/tools/lacp-hash-and-state-reader) shows which flows move when a member fails, and the [spanning tree election calculator](https://ronutz.com/en/tools/stp-election-calculator) which port blocks. Multi-chassis aggregation, stacking and the loop protections are [part 4](https://ronutz.com/en/learn/layer-2-redundancy-lag-mlag-and-spanning-tree).

### The first hop

A host sends everything off its subnet to one address, and RFC 9568 states what losing it means: "Loss of the default router results in a catastrophic event, isolating all end-hosts that are unable to detect an available alternate path" ([RFC 9568, section 1.3](https://www.rfc-editor.org/rfc/rfc9568.txt)). First-hop redundancy protocols move a virtual address and a virtual MAC address between routers so that no host has to notice, in the 3.6 seconds of VRRPv3's defaults or the 9 seconds and more of HSRP's. [First-hop redundancy: VRRP, HSRP, and the gateway that is a fiction](https://ronutz.com/en/learn/first-hop-redundancy-vrrp-and-hsrp) explains the election, the timers and the attacks; [part 5](https://ronutz.com/en/learn/default-gateway-redundancy-vrrpv3-glbp-and-anycast-gateways) takes the subject to scale, with load sharing, tracking, IPv6 and the anycast gateways of EVPN fabrics.

### Layer 3

Routing protocols were built to route around failure, and their own Hellos are slow by design: 40 seconds for OSPF at the sample values and 90 for BGP at the suggested hold time. Equal-cost multipath (ECMP) spreads traffic over several next hops by hashing, and RFC 2992 measures the price of a change in the set of paths as "disruption", the fraction of flows that move ([RFC 2992, November 2000, sections 1 and 2.2](https://www.rfc-editor.org/rfc/rfc2992.txt)). BFD shortens detection, and IP fast reroute shortens the rest: backup routes computed in advance let the router that detects the failure repair it locally "without the immediate need to inform other routers", so that "the disruption time can be limited to the small time taken to detect the adjacent failure and invoke the backup routes" ([RFC 5714, section 1](https://www.rfc-editor.org/rfc/rfc5714.txt)); loop-free alternates are the basic form of those backup routes ([RFC 5286, September 2008](https://www.rfc-editor.org/rfc/rfc5286.txt)). The primers on [OSPF](https://ronutz.com/en/learn/ospf-primer) and [BGP](https://ronutz.com/en/learn/bgp-primer), the two BFD articles and [Anycast: one address in many places](https://ronutz.com/en/learn/anycast) are the background; [part 6](https://ronutz.com/en/learn/layer-3-redundancy-ecmp-bfd-and-fast-reroute) covers ECMP hashing, graceful restart, loop-free alternates and BGP's convergence.

### Stateful devices

Firewalls, load balancers and address translators keep a table of connections, so the stateless router's free failover ends here: a standby that does not have the table drops the connections, and two units that each believe they are active forward the same addresses at once. Fortinet sends heartbeats every 200 milliseconds by default and leaves the failure verdict to a configurable number of missed heartbeats ([Fortinet, Interval between HA heartbeats](https://community.fortinet.com/fortigate-3/technical-tip-interval-between-ha-heartbeats-97919)), 20 by default, so a member is declared dead after 4 seconds ([Fortinet, FortiOS 7.6.6 Administration Guide, HA heartbeat interface](https://docs.fortinet.com/document/fortigate/7.6.6/administration-guide/849059/ha-heartbeat-interface)). The vendor articles describe each implementation: [FortiGate FGCP high availability](https://ronutz.com/en/learn/fortigate-fgcp-ha-clustering), [BIG-IP device trust, device groups and traffic groups](https://ronutz.com/en/learn/bigip-ha-concepts-device-trust-groups), [BIG-IP failover states](https://ronutz.com/en/learn/bigip-failover-states-and-operations), [persistence mirroring across a BIG-IP pair](https://ronutz.com/en/learn/persistence-mirroring-and-ha), [Check Point ElasticXL](https://ronutz.com/en/learn/checkpoint-elasticxl-cluster) and [Check Point management high availability](https://ronutz.com/en/learn/checkpoint-management-high-availability). The [FortiGate HA failover simulator](https://ronutz.com/en/tools/fortigate-ha-failover-simulator) plays an election. [Part 7](https://ronutz.com/en/learn/stateful-clusters-active-standby-active-active-and-split-brain) compares them, with what is and is not synchronized, asymmetric traffic and [split brain](https://ronutz.com/en/glossary/split-brain).

### Application delivery and global load balancing

Above the network, an application delivery controller (ADC) decides which servers are alive by probing them, and global server load balancing (GSLB) decides which site a client reaches, usually by answering DNS queries. The probe is the whole system: [How BIG-IP Local Traffic Manager health monitors decide up or down](https://ronutz.com/en/learn/ltm-health-monitors) and [Load balancing: what actually decides where a request goes](https://ronutz.com/en/learn/load-balancing-what-actually-decides-where-a-request-goes) explain why. DNS-based failover waits for caches, because a resolver may keep an answer for its time to live, up to 2,147,483,647 seconds under RFC 2181 ([RFC 2181, section 8](https://www.rfc-editor.org/rfc/rfc2181.txt)); AWS's account of October 2025 shows that once a corrected record existed, customers reconnected "as cached DNS records expired" ([AWS, Summary of the Amazon DynamoDB Service Disruption in the Northern Virginia (US-EAST-1) Region, October 2025](https://aws.amazon.com/message/101925/)). [GSLB in two tiers](https://ronutz.com/en/learn/gslb-two-tier-pool-then-member) and the [BIG-IP DNS GSLB simulator](https://ronutz.com/en/tools/bigip-dns-gslb-simulator) show the decision; [part 8](https://ronutz.com/en/learn/adc-and-gslb-redundancy-health-monitors-pools-and-site-failover) covers monitors' false verdicts, priority groups, draining and anycast against DNS.

### Data and services

Copies of data are redundancy with a consistency problem. Consensus protocols such as Raft stay available "as long as any majority of the servers are operational and can communicate", so "a typical cluster of five servers can tolerate the failure of any two servers" ([Ongaro and Ousterhout, In Search of an Understandable Consensus Algorithm, extended version, 2014, section 1](https://raft.github.io/raft.pdf)). Replication can also turn a small failure into a large one: in April 2011 a mistaken network change left many of Amazon's Elastic Block Store (EBS) nodes without either network, and when connectivity returned they "rapidly began searching the EBS cluster for available server space where they could re-mirror data", a "re-mirroring storm" that left about 13% of the volumes in the zone stuck ([AWS, Summary of the Amazon EC2 and Amazon RDS Service Disruption in the US East Region, 29 April 2011](https://aws.amazon.com/message/65648/)). A replica copies a deletion as faithfully as a write, which is why [backups are a separate control](https://ronutz.com/en/learn/backups-and-ransomware-recovery). [Part 9](https://ronutz.com/en/learn/data-and-service-redundancy-replication-quorum-rpo-and-rto) covers synchronous and asynchronous replication, [quorum](https://ronutz.com/en/glossary/quorum), and the [recovery point objective (RPO) and the recovery time objective (RTO)](https://ronutz.com/en/glossary/rto-rpo).

### Operations

The last layer is the people and the tools that change everything else, and the outage table shows it is where most of the large failures began. Google's design principles drawn from its own failures include "defense in depth, maintaining consistency across planes, failing open on large failures, carefully preventing and avoiding failures, and assessing root cause quickly" ([Govindan and others, Evolve or Die, SIGCOMM 2016](https://research.google/pubs/evolve-or-die-high-availability-design-principles-drawn-from-googles-network-infrastructure/)). The existing operations articles are the practical side: [blast-radius thinking before a change](https://ronutz.com/en/learn/blast-radius-thinking-before-you-change-anything), [change windows that do not become incidents](https://ronutz.com/en/learn/change-windows-that-do-not-become-incidents), [the first hour of fault isolation](https://ronutz.com/en/learn/fault-isolation-first-hour), [reviewing a network architecture before approving it](https://ronutz.com/en/learn/review-a-network-architecture-before-approving-it), [the hidden assumptions in an architecture diagram](https://ronutz.com/en/learn/hidden-assumptions-in-an-architecture-diagram) and [what belongs in a post-incident technical review](https://ronutz.com/en/learn/what-belongs-in-a-post-incident-technical-review). The [change blast-radius mapper](https://ronutz.com/en/tools/change-blast-radius-mapper) and the [flow path reasoner](https://ronutz.com/en/tools/flow-path-reasoner) structure the same questions. [Part 10](https://ronutz.com/en/learn/testing-redundancy-failure-drills-chaos-and-the-failover-never-tried) is about testing: drills, game days and chaos engineering, and the standby that nobody proved works.

## Landmark outages, and what each taught

Each row below rests on one report written by the operator or by a regulator or parliament. The lesson in the last column is the one the report itself draws or the remedy it commits to, not a verdict of this article. Times are as each report gives them.

| Date | Operator | What happened, in the report's words or close to them | What it taught about redundancy | Report |
|---|---|---|---|---|
| 21 April 2011 | AWS, US East, one zone | A change to upgrade the primary network's capacity shifted traffic onto the lower-capacity redundant EBS network instead of the other primary router; "this change disconnected both the primary and secondary network simultaneously"; 0.07% of the zone's volumes could not be restored | A redundant path sized for less than the primary's load is not a backup for it, and an automatic recovery (re-mirroring) can multiply the load that broke the system | [AWS, 29 April 2011](https://aws.amazon.com/message/65648/) |
| 28 February 2017 | AWS, Simple Storage Service (S3), US-EAST-1 | A playbook command with one input "entered incorrectly" removed more servers than intended; index and placement subsystems needed full restarts that had not been done in the larger regions "for many years"; 09:37 to 13:54 Pacific Standard Time (PST) | The tool now removes capacity more slowly and refuses to take a subsystem below its minimum capacity; recovery itself must be exercised | [AWS, S3 summary](https://aws.amazon.com/message/41926/) |
| 10 March 2021 | OVHcloud, Strasbourg | A fire at the Strasbourg site, whose buildings OVHcloud numbers SBG1 to SBG4; SBG2 powered down and secured, the SBG1 building being dismantled, SBG3 back in operation from 18 March; replacement servers offered in other data centres | A campus is one failure domain for fire; the company's third priority was "Implementing all DRP (Disaster Recovery Plan) mechanisms with our customers" | [OVHcloud, Fire at our Strasbourg Site, update of 2 April 2021](https://us.ovhcloud.com/press/press-releases/2021/fire-our-strasbourg-site) |
| 8 June 2021 | Fastly | A software deployment of 12 May carried a bug that a valid customer configuration change triggered, causing 85% of the network to return errors; detected within one minute, 95% normal within 49 minutes | The same software on every node makes every node one failure domain, however many there are | [Fastly, Summary of June 8 outage](https://www.fastly.com/blog/summary-of-june-8-outage) |
| 4 October 2021 | Meta (Facebook) | A command meant to assess backbone capacity took down all backbone connections; a bug in the audit tool failed to stop it; DNS servers withdrew their BGP routes; out-of-band access was down | The safety check was a single point of failure, and the management path shared the fate of the network it managed (BGP detail in [BGP and the routing chokepoint](https://ronutz.com/en/learn/bgp-and-the-routing-chokepoint)) | [Meta, 5 October 2021](https://engineering.fb.com/2021/10/05/networking-traffic/outage-details/) |
| 8 July 2022 | Rogers, Canada | Staff "removed the Access Control List policy filter from the configuration of the distribution routers"; wireless and wireline shared one IP core; more than 12 million customers lost service, including 9-1-1 calls, from 04:58 on 8 July to 07:00 on 9 July, Eastern Daylight Time (EDT) | Recommendations to separate the management layer "physically and logically" from the data network, separate the cores and test changes more rigorously | [CRTC, Xona Partners assessment, Executive Summary, July 2024](https://crtc.gc.ca/eng/publications/reports/xona2024.htm) |
| 15 August 2023 | Brazil's interconnected grid, Operador Nacional do Sistema Elétrico (ONS) | The 500 kV line Quixadá to Fortaleza II tripped by protection action without a short circuit; the loss of a single line was followed by an abrupt voltage drop because wind and solar plants performed far below what ONS studies, run on the models the plants' owners supplied, had predicted; about 23,368 megawatts (MW) of load interrupted, full restoration authorized at 14:49 | A design that survives the loss of one element on paper depends on models that match the field | [ONS, RAP-ONS 00012/2023, final version of 18 October 2023](https://www.ons.org.br/AcervoDigitalDocumentosEPublicacoes/RAP%202023.08.15%2008h30min%20vers%c3%a3o%20final%20com%20anexos%20de%20diverg%c3%aancia_Final.pdf) |
| 8 November 2023 | Optus, Australia | Routing changes from an international peering network after a routine upgrade "exceeded preset safety levels on key routers"; "almost 90 routers" shut themselves down, "disconnected all these levels of redundancy"; 10.2 million subscribers affected | Identical protective settings on every router made the protection a common-mode failure; Optus told the Senate it "did not have an articulated clear risk" for it | [Senate Environment and Communications References Committee, Optus Network Outage, September 2024, chapter 2](https://www.aph.gov.au/Parliamentary_Business/Committees/Senate/Environment_and_Communications/OptusNetworkOutage/Report/Chapter_2_-_The_Optus_network_outage) |
| 19 July 2024 | CrowdStrike, Windows hosts worldwide | A content update for a new inter-process communication Template Type defined 21 input fields while the code supplied 20; Microsoft estimated 8.5 million Windows devices affected | One security agent on every redundant server is one software version across all of them | [CrowdStrike, Channel File 291 root cause analysis, 6 August 2024](https://www.crowdstrike.com/wp-content/uploads/2024/08/Channel-File-291-Incident-Root-Cause-Analysis-08.06.2024.pdf); [Microsoft, 20 July 2024](https://blogs.microsoft.com/blog/2024/07/20/helping-our-customers-through-the-crowdstrike-outage/) |
| 12 June 2025 | Google Cloud, global | A policy change with blank fields "was replicated globally within seconds" and sent the Service Control binary into a crash loop in every region; a kill switch rolled out within about 40 minutes; us-central1 took up to about 2 h 40 min | Google committed to feature flags for critical binaries and to propagating globally replicated data "incrementally with sufficient time to validate and detect issues" | [Google Cloud Service Health, incident report](https://status.cloud.google.com/incidents/ow5i3PPK96RduMcb1SsW) |
| 19 and 20 October 2025 | AWS, US-EAST-1 | A latent race between two of the DNS Enactors that run "redundantly and fully independently in three different Availability Zones" left an empty DNS record for DynamoDB's regional endpoint, 23:48 to 02:40 Pacific Daylight Time (PDT); Elastic Compute Cloud (EC2) instance launches were impaired until 13:50 | Redundant automation can race itself; independence of instances does not make their shared output independent | [AWS, October 2025](https://aws.amazon.com/message/101925/) |
| 18 November 2025 | Cloudflare | A permissions change on a database cluster made a query return duplicate rows, the Bot Management feature file "doubled in size" and was "propagated to all the machines"; failures from 11:20, core traffic largely normal by 14:30, all systems by 17:06 Coordinated Universal Time (UTC) | A configuration file distributed everywhere is a common cause; the fix was to stop its propagation and insert a known good file | [Cloudflare, Cloudflare outage on November 18, 2025](https://blog.cloudflare.com/18-november-2025-outage/) |

Read down the third column and a pattern appears. Only one row, the fire, is the kind of physical loss that a second device or a second building is designed to absorb; the Brazilian row is a single physical loss that the design was supposed to absorb and did not. Nine of the other ten began with a change, a command, a configuration file or a software version that reached every redundant copy at once, and the tenth with redundant automation that raced itself; that is exactly the shared fate that the arithmetic of independent failures leaves out. Computed from the reports' own times, recovery ran from 49 minutes for 95% of Fastly's network to 26 hours 2 minutes for Rogers, and to 3 days 11 hours 43 minutes, from 00:47 on 21 April to 12:30 on 24 April 2011, before all but 1.04% of the affected EBS volumes had been recovered.

## Questions that find a shared fate

These questions are drawn from the cases above; each one names the report that prompted it.

- **What do the two copies share?** Power, conduit, chassis, software version, configuration source, credentials, management path. AWS lists its own answers for zones ([AWS](https://docs.aws.amazon.com/whitepapers/latest/aws-fault-isolation-boundaries/availability-zones.html)); Rogers's management network shared the core ([CRTC](https://crtc.gc.ca/eng/publications/reports/xona2024.htm)).
- **Can one change reach both?** Staggered deployment is the defence that AWS applies to zones and that Google committed to for replicated data ([Google Cloud](https://status.cloud.google.com/incidents/ow5i3PPK96RduMcb1SsW)).
- **Can the standby carry the load?** The redundant EBS network could not ([AWS, 2011](https://aws.amazon.com/message/65648/)).
- **How long does detection take, and is that in the availability budget?** The timer table above answers the first half; [part 2](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate) answers the second.
- **Does recovery itself work at today's scale?** S3's subsystems had not been fully restarted in years ([AWS, 2017](https://aws.amazon.com/message/41926/)).
- **Do the protective mechanisms act alone or together?** Optus's routers each protected themselves, all at once ([Senate committee](https://www.aph.gov.au/Parliamentary_Business/Committees/Senate/Environment_and_Communications/OptusNetworkOutage/Report/Chapter_2_-_The_Optus_network_outage)).
- **When was the failover last exercised?** That is [part 10](https://ronutz.com/en/learn/testing-redundancy-failure-drills-chaos-and-the-failover-never-tried).

## This series, in order

This article opens the series **Redundant architectures**.

1. **Redundant architectures: how networks survive failure** (this article). What redundancy is for and costs, the failure domains, the layers and the landmark outages.
2. **[The arithmetic of redundancy: availability, MTBF and shared fate](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate)**. Availability, mean time between failures (MTBF) and to repair, nines, series and parallel, N+1 and 2N, k-out-of-n, and why shared fate breaks the sums.
3. **[Physical and power redundancy: feeds, paths and carriers](https://ronutz.com/en/learn/physical-and-power-redundancy-feeds-paths-and-carriers)**. Power supplies and feeds, facility ratings, diverse fibre and carriers, out-of-band management.
4. **[Layer 2 redundancy: LAG, MLAG and spanning tree](https://ronutz.com/en/learn/layer-2-redundancy-lag-mlag-and-spanning-tree)**. Multi-chassis link aggregation (MLAG), stacking, spanning tree convergence and its guards, EVPN multihoming.
5. **[Default gateway redundancy at scale: VRRPv3, GLBP and anycast gateways](https://ronutz.com/en/learn/default-gateway-redundancy-vrrpv3-glbp-and-anycast-gateways)**. The first hop beyond two routers.
6. **[Layer 3 redundancy: ECMP, BFD, graceful restart and fast reroute](https://ronutz.com/en/learn/layer-3-redundancy-ecmp-bfd-and-fast-reroute)**. Multipath, detection, restart and repair paths.
7. **[Stateful clusters: active/standby, active/active and split brain](https://ronutz.com/en/learn/stateful-clusters-active-standby-active-active-and-split-brain)**. Firewall and application delivery clusters across vendors.
8. **[ADC and GSLB redundancy: health monitors, pools and site failover](https://ronutz.com/en/learn/adc-and-gslb-redundancy-health-monitors-pools-and-site-failover)**. Probes, pools, draining, DNS and anycast between sites.
9. **[Data and service redundancy: replication, quorum, RPO and RTO](https://ronutz.com/en/learn/data-and-service-redundancy-replication-quorum-rpo-and-rto)**. Copies, consensus and the objectives that bound loss and downtime.
10. **[Testing redundancy: failure drills, chaos engineering and the failover never tried](https://ronutz.com/en/learn/testing-redundancy-failure-drills-chaos-and-the-failover-never-tried)**. Proving that the standby works.

## What to remember

- Redundancy is an auxiliary means of performing a function; it is active, standby, homogeneous or diverse, and only diversity protects against a fault that every identical copy shares.
- A failure domain is what one fault takes down together, from a power supply to a region; the cloud providers' zone definitions list the shared fates they design against.
- A failover is detection, reaction, propagation, recomputation and reprogramming; detection defaults range from 50 ms for an aggressive BFD session to 90 s for BGP and slow LACP.
- Stateless layers fail over for free; stateful devices need their state synchronized and can end up with two active units.
- Redundancy measurably helps, and measurably less than the diagrams promise: about 40% of the median impact removed in one study, half of operator errors unmasked in another.
- In twelve landmark outages, nine began with a change, a command, a file or a software version that reached every copy at once, and one with redundant automation racing itself; the other two were physical losses, a fire and a single transmission line.

<ReaderQuestions>

- If identical copies protect only against independent faults, and diverse copies double the engineering and testing, where should a network spend its diversity: hardware, software, operators or providers?
- Out-of-band management protects against the network failing, but it is also a second way into every device: how separate should it be, and who should be able to change both?
- Optus's routers each protected themselves correctly and together removed every path; should protective limits be staggered across redundant devices on purpose?
- A post-mortem that names a typo and a post-mortem that names the tool that accepted it describe the same outage: which description leads to the better fix, and why do operators so often publish the first?
- Should regulators set availability figures for networks, as Anatel once did for fixed broadband, or require published post-mortems, as Canada's regulator obtained from Rogers, and which would change designs more?

</ReaderQuestions>

## Sources

- [IEEE Computer Society and ISO/IEC JTC 1/SC 7, SEVOCAB (Software and Systems Engineering Vocabulary), entries redundancy, active redundancy, standby redundancy, homogeneous redundancy and diversity from ISO/IEC/IEEE 24765:2017; definitions copyright 2026 IEEE, used by permission (accessed 16 November 2026)](https://pascal.computer.org/sev_display/index.action)
- [ITU-T Recommendation E.800 (09/2008), Definitions of terms related to quality of service, approved 23 September 2008, in force: sections 3.1.1.5.4 (availability) and 3.1.1.5.5 (reliability) (accessed 16 November 2026)](https://www.itu.int/rec/dologin_pub.asp?lang=e&id=T-REC-E.800-200809-I!!PDF-E&type=items)
- [RFC 4427, Recovery (Protection and Restoration) Terminology for Generalized Multi-Protocol Label Switching (GMPLS), April 2006, Informational: sections 6.1 to 6.3 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc4427.txt)
- [David D. Clark, The Design Philosophy of the DARPA Internet Protocols, SIGCOMM 1988, reprinted in Computer Communication Review, January 1995: fate-sharing (accessed 16 November 2026)](http://ccr.sigcomm.org/archive/1995/jan95/ccr-9501-clark.pdf)
- [Google, Site Reliability Engineering, chapter 3, Embracing Risk: the cost of reliability, the 99% smartphone, the target as minimum and maximum (accessed 16 November 2026)](https://sre.google/sre-book/embracing-risk/)
- [RFC 3439, Some Internet Architectural Guidelines and Philosophy, December 2002, Informational: sections 2, 2.2.2 and 9 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc3439.txt)
- [Phillipa Gill, Navendu Jain and Nachiappan Nagappan, Understanding Network Failures in Data Centers: Measurement, Analysis, and Implications, SIGCOMM 2011: abstract and section 5.1 (accessed 16 November 2026)](https://conferences.sigcomm.org/sigcomm/2011/papers/sigcomm/p350.pdf)
- [David Oppenheimer, Archana Ganapathi and David A. Patterson, Why do Internet services fail, and what can be done about it?, USITS 2003: abstract and section 3.1, read from the PDF's page images (accessed 16 November 2026)](https://www.usenix.org/legacy/events/usits03/tech/full_papers/oppenheimer/oppenheimer.pdf)
- [Justin Meza, Tianyin Xu, Kaushik Veeraraghavan and Onur Mutlu, A Large Scale Study of Data Center Network Reliability, IMC 2018: abstract and major observations (accessed 16 November 2026)](https://conferences.sigcomm.org/imc/2018/papers/imc18-final179.pdf)
- [Google Research, Ramesh Govindan, Ina Minei, Mahesh Kallahalla, Bikash Koley and Amin Vahdat, Evolve or Die: High-Availability Design Principles Drawn from Google's Network Infrastructure, SIGCOMM 2016: abstract (accessed 16 November 2026)](https://research.google/pubs/evolve-or-die-high-availability-design-principles-drawn-from-googles-network-infrastructure/)
- [Amazon Web Services, AWS Fault Isolation Boundaries, Availability Zones, undated web page: independent power, distance, shared fate scenarios, separated deployments (accessed 16 November 2026)](https://docs.aws.amazon.com/whitepapers/latest/aws-fault-isolation-boundaries/availability-zones.html)
- [Microsoft Learn, What are availability zones?, 11 February 2026: separation of zones (accessed 16 November 2026)](https://learn.microsoft.com/en-us/azure/reliability/availability-zones-overview)
- [Google Cloud, Compute Engine, Regions and zones, last updated 10 November 2026: failure domains (accessed 16 November 2026)](https://cloud.google.com/compute/docs/regions-zones)
- [RFC 3386, Network Hierarchy and Multilayer Survivability, November 2002, Informational: section 2.2.2, shared risk group (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc3386.txt)
- [RFC 4202, Routing Extensions in Support of GMPLS, October 2005, Proposed Standard: section 2.3, shared risk link group (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc4202.txt)
- [Daniel Ford and others (Google), Availability in Globally Distributed Storage Systems, OSDI 2010: sections 1 and 4, failure bursts and failure domains (accessed 16 November 2026)](https://www.usenix.org/legacy/event/osdi10/tech/full_papers/Ford.pdf)
- [RFC 5714, IP Fast Reroute Framework, January 2010, Informational: sections 1 and 4 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc5714.txt)
- [RFC 5286, Basic Specification for IP Fast Reroute: Loop-Free Alternates, September 2008, Proposed Standard, updated by RFC 8518 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc5286.txt)
- [Extreme Networks, SLX-OS 20.x Layer 2 configuration, Configuring the LACP timeout period: 3 and 90 seconds (accessed 16 November 2026)](https://documentation.extremenetworks.com/slxos/SW/20xx/l2config/GUID-67DF739B-2115-4055-92BE-D1DB02F72B70.shtml)
- [The Linux kernel documentation, Linux Ethernet Bonding Driver HOWTO: lacp_rate, slow by default (accessed 16 November 2026)](https://docs.kernel.org/networking/bonding.html)
- [Cisco, Understand Rapid Spanning Tree Protocol (802.1w), document 24062, updated 9 February 2023: 802.1D forward delay, three missed BPDUs, RSTP convergence (accessed 16 November 2026)](https://www.cisco.com/c/en/us/support/docs/lan-switching/spanning-tree-protocol/24062-146.html)
- [RFC 9568, Virtual Router Redundancy Protocol (VRRP) Version 3 for IPv4 and IPv6, April 2024, Proposed Standard: sections 1.3, 3 and 6.1 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc9568.txt)
- [RFC 2281, Cisco Hot Standby Router Protocol (HSRP), March 1998, Informational: section 5.1, Hellotime and Holdtime (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc2281.txt)
- [FRRouting documentation, BFD: default intervals and multiplier (accessed 16 November 2026)](https://docs.frrouting.org/en/latest/bfd.html)
- [RFC 5880, Bidirectional Forwarding Detection (BFD), June 2010, Proposed Standard: section 7 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc5880.txt)
- [RFC 2328, OSPF Version 2, April 1998, Internet Standard: appendix C.3, HelloInterval and RouterDeadInterval (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc2328.txt)
- [RFC 4271, A Border Gateway Protocol 4 (BGP-4), January 2006: section 10, suggested HoldTime and KeepaliveTime (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc4271.txt)
- [Fortinet Community, Technical Tip: Interval between HA heartbeats, updated 7 September 2026: 200 ms by default (accessed 16 November 2026)](https://community.fortinet.com/fortigate-3/technical-tip-interval-between-ha-heartbeats-97919)
- [Fortinet, FortiOS 7.6.6 Administration Guide, HA heartbeat interface: 20 consecutive lost heartbeats by default, 2 × 100 ms × 20 = 4 s (accessed 16 November 2026)](https://docs.fortinet.com/document/fortigate/7.6.6/administration-guide/849059/ha-heartbeat-interface)
- [RFC 1035, Domain Names: Implementation and Specification, November 1987, Internet Standard: section 3.2.1, TTL (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc1035.txt)
- [RFC 2181, Clarifications to the DNS Specification, July 1997: section 8, TTL range (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc2181.txt)
- [Anatel, Resolução nº 715, de 23 de outubro de 2019, Title VI-A on data centres, as amended by Resolução nº 780 of 1 August 2025, with the note on Acórdão nº 58 of 3 March 2026 (accessed 16 November 2026)](https://informacoes.anatel.gov.br/legislacao/resolucoes/2019/1350-resolucao-717)
- [Meta Engineering, Santosh Janardhan, More details about the October 4 outage, 5 October 2021 (accessed 16 November 2026)](https://engineering.fb.com/2021/10/05/networking-traffic/outage-details/)
- [CRTC, Assessment of Rogers Networks for Resiliency and Reliability Following the 8 July 2022 Outage, Executive Summary, July 2024 (accessed 16 November 2026)](https://crtc.gc.ca/eng/publications/reports/xona2024.htm)
- [IEEE 802.1AX-2020, Link Aggregation, project page: LAG definition, DRNI, approval on 30 January 2020 (accessed 16 November 2026)](https://1.ieee802.org/tsn/802-1ax-rev/)
- [RFC 7432, BGP MPLS-Based Ethernet VPN, February 2015, Proposed Standard: section 3, Single-Active and All-Active redundancy modes (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc7432.txt)
- [RFC 2992, Analysis of an Equal-Cost Multi-Path Algorithm, November 2000, Informational: sections 1 and 2.2 (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc2992.txt)
- [Amazon Web Services, Summary of the Amazon DynamoDB Service Disruption in the Northern Virginia (US-EAST-1) Region, October 2025: DNS Enactors in three zones, the empty record, times (accessed 16 November 2026)](https://aws.amazon.com/message/101925/)
- [Diego Ongaro and John Ousterhout, In Search of an Understandable Consensus Algorithm (Extended Version), Stanford University, 2014: sections 1 and 5.1 (accessed 16 November 2026)](https://raft.github.io/raft.pdf)
- [Amazon Web Services, Summary of the Amazon EC2 and Amazon RDS Service Disruption in the US East Region, 29 April 2011 (accessed 16 November 2026)](https://aws.amazon.com/message/65648/)
- [Amazon Web Services, Summary of the Amazon S3 Service Disruption in the Northern Virginia (US-EAST-1) Region, event of 28 February 2017 (accessed 16 November 2026)](https://aws.amazon.com/message/41926/)
- [OVHcloud, Fire at our Strasbourg Site, press release, update of 2 April 2021 (accessed 16 November 2026)](https://us.ovhcloud.com/press/press-releases/2021/fire-our-strasbourg-site)
- [Fastly, Nick Rockwell, Summary of June 8 outage, 8 June 2021 (accessed 16 November 2026)](https://www.fastly.com/blog/summary-of-june-8-outage)
- [Operador Nacional do Sistema Elétrico (ONS), RAP-ONS 00012/2023, Análise da perturbação do dia 15/08/2023 às 08h30min, final version with annexes of divergence, 18 October 2023: chapter 1 and finding 5.1.36 (accessed 16 November 2026)](https://www.ons.org.br/AcervoDigitalDocumentosEPublicacoes/RAP%202023.08.15%2008h30min%20vers%c3%a3o%20final%20com%20anexos%20de%20diverg%c3%aancia_Final.pdf)
- [Parliament of Australia, Senate Environment and Communications References Committee, Optus Network Outage, report of September 2024, chapter 2 (accessed 16 November 2026)](https://www.aph.gov.au/Parliamentary_Business/Committees/Senate/Environment_and_Communications/OptusNetworkOutage/Report/Chapter_2_-_The_Optus_network_outage)
- [CrowdStrike, External Technical Root Cause Analysis, Channel File 291, 6 August 2024 (accessed 16 November 2026)](https://www.crowdstrike.com/wp-content/uploads/2024/08/Channel-File-291-Incident-Root-Cause-Analysis-08.06.2024.pdf)
- [Microsoft, David Weston, Helping our customers through the CrowdStrike outage, 20 July 2024: 8.5 million devices (accessed 16 November 2026)](https://blogs.microsoft.com/blog/2024/07/20/helping-our-customers-through-the-crowdstrike-outage/)
- [Google Cloud Service Health, incident ow5i3PPK96RduMcb1SsW, Multiple GCP products, 12 June 2025: mini incident report, remediation (accessed 16 November 2026)](https://status.cloud.google.com/incidents/ow5i3PPK96RduMcb1SsW)
- [Cloudflare Blog, Matthew Prince, Cloudflare outage on November 18, 2025, 18 November 2025 (accessed 16 November 2026)](https://blog.cloudflare.com/18-november-2025-outage/)