# Physical and power redundancy: feeds, paths and carriers

> Every protocol in this series assumes a second box, a second cable and a second source of power that do not fail together. How power redundancy is counted in a switch and behind it, what the Uptime Institute's tiers and TIA-942 promise and what they do not, why two fibres or two carriers can share one trench, why the management network must survive the outage it is meant to fix, and the trade between a chassis with redundant supervisors and many fixed switches, each from the operators' and regulators' own reports. After reading, you can size supplies against A and B feeds, ask a carrier the questions that expose a shared path, and spot the common cause hiding behind two of everything.

Source: https://ronutz.com/en/learn/physical-and-power-redundancy-feeds-paths-and-carriers  
Updated: 2026-11-23  
Related tools: https://ronutz.com/en/tools/change-blast-radius-mapper, https://ronutz.com/en/tools/flow-path-reasoner, https://ronutz.com/en/tools/time-calculator, https://ronutz.com/en/tools/cable-run-planner, https://ronutz.com/en/tools/incident-timeline-rca-builder

---

Every protocol in this series, from link aggregation to global load balancing, assumes that the second box, the second cable and the second source of power do not fail at the same moment as the first. That assumption is physical, and it is the one most often broken: two power supplies on one feed, two fibres in one trench, two carriers in one duct, a management network that runs over the network it is meant to rescue. This part of the series goes through the physical layer of redundancy from the power supply up: how power is counted in a switch and behind it, what the facility ratings promise, how paths and carriers share fate, why out-of-band access has to survive the outage, and what a chassis with two supervisors buys against many fixed switches. After reading, you can size supplies against A and B feeds, read a tier or rating claim for what it says, ask a carrier the questions that reveal a shared path, and look for the common cause behind two of everything. The arithmetic of availability, series and parallel, is in [part 2 of this series](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate); this part keeps to the things it counts.

## Power at the device: supplies, feeds and the arithmetic

Most network equipment accepts more than one power supply, and the vendors count the redundancy in two ways. Juniper's EX switches manage power by default "for N+1 redundancy, in which one power supply is held in reserve for backup if one of the other power supplies is removed or fails", and can instead be set for N+N, in which "power management holds N power supplies in reserve for backup"; with six supplies, N+N gives "three power supplies available for normal operating power and reserves three power supplies for redundancy (3+3)", and with an odd number the extra one goes to operating power, so five supplies make 3+2 ([Juniper Networks, Junos OS High Availability User Guide, published 15 November 2026, power supply redundancy](https://www.juniper.net/documentation/us/en/software/junos/high-availability/high-availability.pdf)). Cisco's Catalyst 9400 chassis describe the same two modes with the feeds named: "N + 1 redundancy with N independent input circuits" and "N + N redundancy with N independent input circuits", with four power supply bays in the C9404R and eight in the C9407R and C9410R ([Cisco, Catalyst 9400 Series switches data sheet, updated 1 September 2026](https://www.cisco.com/c/en/us/products/collateral/switches/catalyst-9400-series-switches/nb-06-cat9400-ser-data-sheet-cte-en.html)).

Juniper's table makes the cost visible, with n watts per supply (Juniper, as above):

| Supplies installed | Operating power, N+1 | Operating power, N+N |
|---|---|---|
| 2 | 1 × n W | 1 × n W |
| 3 | 2 × n W | 2 × n W |
| 4 | 3 × n W | 2 × n W |
| 5 | 4 × n W | 3 × n W |
| 6 | 5 × n W | 3 × n W |

The difference between the two columns is the difference between losing a supply and losing a feed. A worked example, with round numbers chosen for the arithmetic rather than taken from any product: a chassis draws 2,600 W and each supply gives 1,000 W.

- **Four supplies in N+1** offer 3 × 1,000 = 3,000 W of operating power, enough for 2,600 W with one supply failed.
- **The same four supplies wired two to feed A and two to feed B** lose two at once when feed A fails, leaving 2 × 1,000 = 2,000 W for a 2,600 W load: N+1 protected against a failed supply, not against a failed feed.
- **Six supplies in N+N, three on each feed,** keep 3 × 1,000 = 3,000 W when either feed fails.

That is why Cisco names the input circuits in its definition: N+N is meant to survive the loss of a whole circuit. The same logic applies to cooling, where the Catalyst 9400's fan trays "are composed of multiple independently controlled fans with N+1 redundancy", so that "If any single fan fails, the system will continue to operate without a degradation in cooling" (Cisco, data sheet, as above). Two supplies plugged into one power strip, or two strips fed from one circuit, are one supply as far as the feed is concerned.

## Behind the socket: UPS, generators and the minutes between them

Behind the A and B feeds sit the facility's sources: the utility, a battery-backed uninterruptible power supply (UPS) that bridges the gap, and generators that take over if the outage lasts. The reports operators publish after failures show where that chain breaks, and it is rarely where the diagram puts the redundancy.

**The generator that would not take the load.** On 29 June 2012 a storm hit Northern Virginia, and at 7:24 pm Pacific Daylight Time "a large voltage spike was experienced by the electrical switching equipment in two of the US East-1 datacenters"; in one of them "the generators started successfully, but each generator independently failed to provide stable voltage as they were brought into service", so the servers ran on UPS power ([Amazon Web Services, Summary of the AWS Service Event in the US East Region, 2 July 2012](https://aws.amazon.com/message/67457/)). Utility power failed a second time at 7:57 pm, the generators again failed to take the load, and "the UPS systems were depleting and servers began losing power at 8:04pm PDT" (AWS, as above). From 7:57 to 8:04 is seven minutes, the margin the batteries gave. The equipment was not neglected: the generators were "all the same brand", less than two years old, "tested weekly", and the whole data centre had run on them in a full load test on 12 May that year (AWS, as above). AWS's changes were to "lengthen the amount of time the electrical switching equipment gives the generators to reach stable power", to "expand the power quality tolerances", and to have enough staff on site to switch to generator manually "before UPSs discharge" (AWS, as above). Seven minutes is a planning number: the [time calculator](https://ronutz.com/en/tools/time-calculator) does the arithmetic of such windows exactly.

**Two generators that were really one.** The same storm, the derecho of June 2012, cut emergency calls in Northern Virginia, and the United States Federal Communications Commission (FCC) investigated. Its bureau found that "9-1-1 communications were disrupted in large part because of avoidable planning and system failures, including the lack of functional backup power, notably in central offices" ([FCC Public Safety and Homeland Security Bureau, Impact of the June 2012 Derecho on Communications Networks and Services, January 2013](https://docs.fcc.gov/public/attachments/DOC-318331A1.pdf)). According to the operator, "nine out of 136 central-office backup generators" in the affected area did not work, "about 7 percent" (FCC, as above). In Arlington, the backup system "includes two generators that must operate in tandem to power the facility, which contravenes CSRIC best practice 8-7-5281", a practice of the FCC's Communications Security, Reliability and Interoperability Council (CSRIC) that each generator be "a standalone unit that is not dependent on the operation of another generator for proper functioning, including fuel supply path" (FCC, as above). One generator "failed to start because air had entered the fuel system", the second "became overloaded and automatically shut down", and the office "ran on battery power for approximately six hours until the batteries ran out around 5:00 a.m." (FCC, as above). Two generators that both had to run were a design with no spare, however many machines stood in the room.

**The monitoring that died first.** The Arlington office also linked the operator's network operations centres (NOCs) to thirty-four sites, and "Backup power for the monitoring equipment in Arlington was provided by a UPS that lasts only thirty minutes", so the operator lost sight of its network in the region half an hour after the generators failed, while the rest of the office still ran on batteries (FCC, as above). The bureau's recommendation was blunt: providers should "have diverse monitor and control links and capabilities throughout the network" (FCC, as above).

**Batteries that held, data that did not.** On 13 August 2015, "four successive lightning strikes on the local utilities grid that powers our European datacenter caused a brief loss of power to storage systems" in Google's europe-west1-b zone; the systems had battery backup, but some recently written data "was located on storage systems which were more susceptible to power failure from extended or repeated battery drain", and in "less than 0.000001% of PD space" there was permanent data loss, PD being Google's persistent disk ([Google Cloud, Google Compute Engine Persistent Disk issue in europe-west1-b, incident 15056, 2015](https://status.cloud.google.com/incident/compute/15056)). About 5 percent of standard persistent disks in the zone saw at least one input or output error during the incident, and Google's reminder to customers was that resources in one zone "exist in a single Google datacenter and are therefore unavoidably vulnerable to datacenter-scale disasters" (Google Cloud, as above).

**A power sag that stopped the cooling.** On 30 August 2023, "a utility voltage sag was caused by a lightning strike on electrical infrastructure approximately 18 miles from the impacted Availability Zone" of Microsoft's Australia East region, and the sag "caused cooling system chillers for multiple datacenters to shut down"; 13 failed to restart and had to be restarted by hand on the roof, one group after another ([Microsoft Azure, Post Incident Review, Services impacted after power/cooling issue, Australia East, tracking ID VVTQ-J98](https://azure.status.microsoft/en-us/status/history/?trackingid=VVTQ-J98)). The two data halls affected "require at least four chillers to be operational", and before the sag there were "seven chillers, with five chillers in operation and two chillers in standby"; by the time the team reached the last five, their water was too hot to allow a restart (Azure, as above). On paper, four needed out of seven installed leaves three to spare, N+3; in practice, one electrical event tripped them together, and the spare capacity depended on how fast people could walk a roof. The halls' equipment had to be shut down to stop "thermal runaway", and full mitigation took until 3 September (Azure, as above).

**A leak in the UPS room.** On 25 April 2023, "a cooling system water pipe leak occurred in one of the data centers in the europe-west9 region", the leak "entered an associated uninterruptible power supply (UPS) room, and led to a fire", and the fire service ordered "a power shutdown of the entire data center building for several hours" ([Google Cloud, Multiple Google Cloud services in the europe-west9-a zone are impacted, Paris, 2023](https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY)). The region had "three buildings with independent cooling, power, and networking", but a regional database's replicas "were not correctly distributed across the three buildings in the region to ensure quorum was available after the impacted building was powered down", so one building's power took down the control plane of the whole region (Google Cloud, as above). The physical design was redundant; a placement decision three layers up undid it.

The aggregate picture agrees with the cases. The Uptime Institute's analysis of 2025 states that "Power remains the leading cause of impactful outages", with IT and networking issues at "23% of impactful outages" in 2024, drawing on "multiple surveys, information supplied by Uptime Institute members and partners, and its database of publicly reported outages" ([Uptime Institute, press release, Uptime Announces Annual Outage Analysis Report 2025, 6 May 2025](https://www.businesswire.com/news/home/20250506733553/en/Uptime-Announces-Annual-Outage-Analysis-Report-2025)).

**What regulators require.** For the providers of emergency call service, the FCC turned the derecho's lessons into rules. A central office that directly serves a public safety answering point must have backup power "for at least 24 hours at full office load", and one that hosts a selective router "for at least 72 hours at full office load", "including all equipment design, proper installation, necessary testing, and equipment maintenance"; newer IP elements meet the benchmark with "an uninterruptible and continuous power supply and automatic switchover to geographically diverse backup facilities" ([United States, Code of Federal Regulations, title 47, section 9.19, Provision of reliable 911 service, eCFR current text](https://www.ecfr.gov/api/renderer/v1/content/enhanced/current/title-47?part=9&section=9.19)).

## Facility ratings: the Uptime Institute's tiers and TIA-942

Two rating systems describe how redundant a data centre's power, cooling and pathways are, and both are often quoted as if they were availability figures.

The Uptime Institute's tiers describe topology. In its own words, Tier I is "the basic capacity level", and "The facility will have to shut down completely for preventive maintenance and repairs"; Tier II adds "redundant capacity components for power and cooling", but "unexpected shutdown of a Tier II data center will affect the system"; "A Tier III data center is concurrently maintainable", and such facilities "require no shutdowns when equipment needs maintenance or replacement"; and "Tier IV facilities add fault tolerance to the Tier III topology", so that "When a piece of equipment fails, or there is an interruption in the distribution path, IT operations will not be affected" ([Uptime Institute, Tier Classification System](https://uptimeinstitute.com/tiers)). The institute reports "over 4300 Tier Certifications issued in 120+ countries" (Uptime Institute, as above).

| Tier | Uptime Institute's name for it | Maintenance without shutdown? | A single failure without impact? |
|---|---|---|---|
| I | Basic capacity | No | No |
| II | Redundant capacity components | Components, not paths | No |
| III | Concurrently maintainable | Yes | Not promised |
| IV | Fault tolerant | Yes | Yes, including a distribution path |

The tiers carry no percentage. In 2019 the institute's research director wrote that its chief technology officer, Chris Brown, explains "there is not a direct relationship between any number of 'nines' and a Tier level", that "Early on, Uptime did publish a paper with some 'expected' availability numbers for each Tier level" but "this is no longer considered relevant", and Brown's reason: "it is possible to create a mathematical model to show a data center has a good level of availability" "while still having multiple single points of failure in its design" ([Andy Lawrence, Uptime Institute Journal, 99 Red Flags: The Availability Nines, 28 October 2019](https://journal.uptimeinstitute.com/?p=6064)). The same article lists why availability figures mislead: no stated period, varying definitions of downtime, maintenance left out, and a figure "set to maximize profit for the operator" in service agreements (Lawrence, as above). Documents still quote percentages next to tiers: B3, the Brazilian exchange, describes its Santana de Parnaíba data centre as holding a "Tier III certificate, provided by the Uptime Institute" (our translation here and below), and, in the same sentence block, a "redundancy capacity of 99.98%" ([B3, Commercial Policy for Co-location Services (in Portuguese), version 3.5, 15 January 2024](https://sistemasweb.b3.com.br/normativos/POLITICA%20COMERCIAL%20COLOCATION%20-%20PORTUGUES.PDF)). The two statements answer different questions, one about topology and one about a number, and the Uptime Institute's own position is that the second does not follow from the first.

The Telecommunications Industry Association's standard ANSI/TIA-942, published through the American National Standards Institute (ANSI) process, rates data centre infrastructure instead. Revision C appeared in May 2024, "the third revision since the inception of the original ANSI/TIA-942 standard" ([TIA, TIA Unveils Revision C of the Global Data Center Infrastructure Standard, 9 May 2024](https://tiaonline.org/news/tia-unveils-revision-c-of-the-global-data-center-infrastructure-standard/)), and TIA's certification checks facilities against "four rated levels of reliability"; an addendum on artificial intelligence workloads is in preparation, with publication targeted for mid-2027 ([TIA, TIA Advances AI Ready Data Centers with New ANSI/TIA 942 Addendum, Global Certification Leadership, and Expanded Industry Quality Initiative, 24 March 2026](https://tiaonline.org/news/tia-advances-ai-ready-data-centers-with-new-ansi-tia-942-addendum-global-certification-leadership-and-expanded-industry-quality-initiative/)). The definitions of the four levels are in the standard itself, which was not among the pages read for this article.

A Brazilian buyer meets both. B3's colocation document names the Uptime certificate, as quoted above, and the site's articles on [the exchange's electronic access](https://ronutz.com/en/learn/brazil-bmf-bovespa-b3-and-electronic-access) and [colocation and latency](https://ronutz.com/en/learn/colocation-microwaves-and-the-race-for-latency) describe the two data centres it pairs. The standards of the Associação Brasileira de Normas Técnicas (ABNT) that apply to cabling and data centre facilities in Brazil are sold through a catalogue that could not be read for this article; they are listed as a gap rather than described from memory.

## Paths: diverse fibre, shared trenches and the SRLG

Two links are only as independent as the ground they run through. The routing standards have a name for the problem: in RFC 4202 (October 2005), "A set of links may constitute a 'shared risk link group' (SRLG) if they share a resource whose failure may affect all links in the set. For example, two fibers in the same conduit would be in the same SRLG" ([RFC 4202, Routing Extensions in Support of Generalized Multi-Protocol Label Switching (GMPLS), section 2.3](https://www.rfc-editor.org/rfc/rfc4202.txt)). A path computation asked for diverse paths "should attempt to route the paths so that they do not have any links in common, and such that the path SRLGs are disjoint" (RFC 4202, as above). RFC 3386 (November 2002) widens the idea to a shared risk group, "a set of network elements that are collectively impacted by a specific fault or fault type", including "shared fiber cable, shared right of way, shared optical ring, shared office without power sharing" ([RFC 3386, Network Hierarchy and Multilayer Survivability, section 2.2](https://www.rfc-editor.org/rfc/rfc3386.txt)).

A regulator has written the test down. Under the FCC's 911 reliability rule, "Circuits or paths are physically diverse if they provide more than one physical route between end points with no common points where a single failure at that point would cause both circuits or paths to fail. Circuits or paths that share a common segment such as a fiber-optic cable or circuit board are not physically diverse even if they are logically diverse for purposes of transmitting data" (47 CFR 9.19, as above). The rule also names the slow enemy of diversity, rearrangement: legacy circuits must be tagged in inventory "to make it less likely that circuit rearrangements will compromise diversity", and providers certify diversity through yearly "diversity audits" (47 CFR 9.19, as above). The derecho report shows why: Fairfax County's emergency centre was "served by redundant selective routers", but "this redundancy was compromised as a result of the transport failures caused by the generator failure in Verizon's Fairfax central office and other single points of failure", and the bureau concluded that a diversity audit, "as called for in CSRIC best practice 8-7-0532", might have found them; that practice says "network operators should periodically audit the physical and logical diversity called for by network design and take appropriate measures as needed" (FCC, derecho report, as above).

How common shared trenches are was measured in a peer-reviewed study of the long-haul fibre of the United States. Building a map from providers' own fibre maps and public records, the authors found 542 distinct conduits and that "89.67%, 63.28% and 53.50% of the conduits are shared by at least two, three and four major ISPs", internet service providers, out of the twenty studied; "12 out of 542 conduits are shared by more than 17 ISPs", such as Salt Lake City to Denver and Philadelphia to New York ([Durairajan, Barford, Sommers and Willinger, InterTubes: A Study of the US Long-haul Fiber-optic Infrastructure, ACM SIGCOMM 2015, London, 17 to 21 August 2015](https://pages.cs.wisc.edu/~pb/tubes_final.pdf)). Their conclusion: "the US long-haul infrastructure lacks much of the diversity that is a hallmark of all the commonly-known models and maps of the more logical Internet topologies" (Durairajan and others, as above). The sea has the same problem at a larger scale, told in [submarine cables and the physical internet](https://ronutz.com/en/learn/submarine-cables-and-the-physical-internet).

A worked example shows why one shared stretch dominates everything else. Suppose, as round illustrative inputs rather than measured rates, that each of two routes has a 1 percent chance in a year of being cut somewhere along its own length, and that the two meet for a short stretch in one trench with a 0.5 percent chance of being cut in the same year.

- **Fully independent routes:** both are cut in the same year with probability 0.01 × 0.01 = 0.0001, one year in ten thousand.
- **With the shared stretch:** service is lost if the shared stretch is cut, or if both separate parts are: 1 − (1 − 0.005) × (1 − 0.0001) = 1 − 0.995 × 0.9999 ≈ 0.0051, about one year in two hundred.

The shared stretch makes the pair about fifty times more likely to fail together, and it is fifty times larger than the risk the redundancy was bought to remove. The series and parallel formulas behind this are in [part 2](https://ronutz.com/en/learn/the-arithmetic-of-redundancy-availability-mtbf-and-shared-fate); the physical point is that no amount of capacity on either route changes the result, only the route does.

## Carriers: two contracts are not two paths

Buying a second carrier is the commonest form of path redundancy and the easiest to get wrong, because carriers lease each other's fibre and share each other's ducts, as the conduit study measured. The safeguard is to ask for physical diversity, not for a second contract. B3 writes the requirement into its access manual for the brokers, banks and dealers connected to it: "To mitigate risks associated with a single point of failure, it is mandatory to contract ... two distinct network providers that use distinct physical routes", with an exception only for places "not served by distinct providers that have distinct routes" ([B3, Manual for Access to the Technology Infrastructure (in Portuguese), version 8.5, 13 February 2026](https://b3.com.br/data/files/B9/F0/1F/4F/DC7CF91094DCD8F9AC094EA8/2026%20-%20Manual%20de%20Acesso%20a%20Infraestrutura%20Tecnologica%20da%20B3.pdf)). Its access forms then build up the redundancy layer by layer: two links and two routers to the exchange's two data centres through two distinct carriers, then links from two of the participant's own sites, then two links per site, each pair from different carriers, so that "an instability in one carrier's network" cannot interrupt access (B3, as above). The same manual asks for a first-hop redundancy protocol on the participant's routers and warns that VRRP and HSRP do not interoperate; the reason is in [first-hop redundancy](https://ronutz.com/en/learn/first-hop-redundancy-vrrp-and-hsrp).

The questions that expose a shared path follow from the definitions above. Where does each route leave the building, and through which duct? Which central offices, exchanges or junction boxes do the two routes pass through? Which shared risk link groups does each carrier assign to each circuit? Are any segments leased from the other carrier? Who audits the diversity after the circuits are installed, and will the carrier report a rearrangement that merges them? The FCC's rules for emergency service answer the last two with yearly audits and inventory tags (47 CFR 9.19, as above); outside that service, the customer has to ask. The [flow path reasoner](https://ronutz.com/en/tools/flow-path-reasoner) helps write the path down hop by hop before asking.

**What Brazilian regulation says about continuity.** In Brazil the carrier's obligation depends on the regime. Anatel's general regulation of telecommunications services states that services in the public regime are those "whose existence, universalization and continuity the Union itself undertakes to ensure", while "Telecommunications services operated under the private regime are not subject to obligations of universalization and continuity, nor to provision guaranteed by the Union" ([Anatel, Resolução nº 777 of 28 April 2025, Regulamento Geral dos Serviços de Telecomunicações (RGST), article 5](https://informacoes.anatel.gov.br/legislacao/resolucoes/2025/2022-resolucao-777)). The quality regulation, the Regulamento de Qualidade dos Serviços de Telecomunicações (RQUAL), defines an interruption as a stoppage "resulting from any failure in the provider's network that prevents enjoyment of the service", and a massive interruption as one "of wide scope or that affects a significant number of users"; a provider must inform the public, Anatel and interconnected providers of an unplanned massive interruption "within 24 (twenty-four) hours of the start of the event", and must refund affected users automatically, "in proportion to the time interrupted" ([Anatel, Resolução nº 717 of 23 December 2019, RQUAL, articles 3, 30 and 32](https://informacoes.anatel.gov.br/legislacao/resolucoes/2019/1371-resolucao-717)). Anatel's cybersecurity regulation for the sector, the Regulamento de Segurança Cibernética Aplicada ao Setor de Telecomunicações (R-Ciber), lists "Diversity" among its principles and defines critical telecommunications infrastructures as those whose interruption or destruction "will cause serious social, economic, political or international impact, or impact on the security of the State and of society" ([Anatel, Resolução nº 740 of 21 December 2020, R-Ciber, articles 3 and 4](https://informacoes.anatel.gov.br/legislacao/resolucoes/2020/1497-resolucao-740)). None of these requires a customer's two circuits to be diverse; a refund pays for an outage, it does not prevent one. Who governs the Brazilian internet more broadly is described in [who actually governs the internet in Brazil](https://ronutz.com/en/learn/brazil-internet-governance).

## Out-of-band management: the path you need when the others are gone

The network an operator uses to repair the network has to survive the failure being repaired. Three operators' accounts show the same lesson from three directions.

- **A hospital.** Among John Halamka's lessons from the 2002 collapse at Beth Israel Deaconess: "I did not know that we needed 'out of band' tools to gain insight into the problems with the network. In effect, we required the network to be functional to diagnose problems with the network" ([John Halamka, The CareGroup Network Outage, 4 March 2008](https://geekdoctor.blogspot.com/2008/03/caregroup-network-outage.html)). The layer 2 side of that outage is told in [part 4 of this series](https://ronutz.com/en/learn/layer-2-redundancy-lag-mlag-and-spanning-tree).
- **A social network.** On 4 October 2021, a command meant to assess backbone capacity "unintentionally took down all the connections in our backbone network", and Meta's engineering vice-president wrote that "Our primary and out-of-band network access was down, so we sent engineers onsite to the data centers", where physical security added time: "They're hard to get into, and once you're inside, the hardware and routers are designed to be difficult to modify even when you have physical access to them" ([Santosh Janardhan, Meta Engineering, More details about the October 4 outage, 5 October 2021](https://engineering.fb.com/2021/10/05/networking-traffic/outage-details/)).
- **A national carrier.** The outage at Rogers in Canada "lasted from 4:58 EDT on 8 July 2022 to 7:00 EDT on 9 July 2022", Eastern Daylight Time, about 26 hours, and "More than 12 million customers lost wireless and wireline services"; the assessment commissioned by the Canadian Radio-television and Telecommunications Commission (CRTC) found that "Rogers had a management network that relied on the Rogers IP core network", so "remote Rogers employees were unable to access the management network" and staff had to "dispatch staff to remote sites to physically access the affected routers" ([Xona Partners for the CRTC, Assessment of Rogers Networks for Resiliency and Reliability Following the 8 July 2022 Outage, Executive Summary, July 2024](https://crtc.gc.ca/eng/publications/reports/xona2024.htm)).

The CRTC report draws the design rules: "network resiliency demands that telecom network operators have secure alternative access to crucial remote network elements that is not dependent on the data network", "Separate the network management layer physically and logically from the data network", and give the operations centre "redundant connectivity from alternative service providers for network management" (Xona Partners, as above). The FCC's derecho report adds power to the list, by counterexample: monitoring equipment on a thirty-minute UPS in an office that ran six hours on batteries (FCC, derecho report, as above). An out-of-band network is a redundancy design of its own, and it fails the same way the others do: if it shares a path, a power source or a control plane with the production network, it is not out of band in the failure that matters. How to build that path, from the console cable to the confirmed commit, is in [out-of-band management and the console](https://ronutz.com/en/learn/out-of-band-management-and-the-console).

## Inside the box: supervisors, line cards and switchover

A modular chassis duplicates its brain. The Catalyst 9400 chassis "support 1+1 supervisor-engine redundancy", in which "The secondary supervisor engine serves as a standby, monitoring the operation of the primary supervisor engine", able "to immediately take over in subsecond time if the primary engine fails"; with two supervisors, an in-service software upgrade (ISSU) upgrades software "with minimal (less than 200 msec) to no disruption to the network" (Cisco, data sheet, as above).

Juniper documents what such a switchover does and does not keep. Its graceful Routing Engine switchover (GRES) "enables a device with redundant Routing Engines to continue forwarding packets even if one Routing Engine fails", and "If the backup Routing Engine does not receive a keepalive from the primary Routing Engine after 2 seconds, it determines that the primary Routing Engine has failed"; the forwarding hardware reconnects to the new primary, "Does not reboot" and "Does not interrupt traffic" ([Juniper Networks, understanding graceful Routing Engine switchover](https://www.juniper.net/documentation/us/en/software/junos/high-availability/topics/concept/gres-overview.html)). But "GRES does not preserve the control plane": to keep routing during the switchover it "must be combined with either" graceful restart protocol extensions or nonstop active routing (NSR), and "NSR/GRES performance is limited by the slowest Routing Engine in the system" (Juniper, as above). How graceful restart and nonstop forwarding behave towards neighbours is the subject of [part 6 of this series](https://ronutz.com/en/learn/layer-3-redundancy-ecmp-bfd-and-fast-reroute).

Line cards are a shared risk inside the box. Juniper's nonstop software upgrade (NSSU) upgrades line cards or Virtual Chassis members one at a time, and the guide's advice applies beyond upgrades: "By configuring LAGs such that the member links reside on different line cards or Virtual Chassis members, you can achieve minimal traffic disruption when performing an NSSU" (Juniper, High Availability User Guide, as above). A link aggregation group (LAG) whose members share one line card is a bundle with one point of failure; [link aggregation and LACP](https://ronutz.com/en/learn/link-aggregation-and-lacp) explains how the bundle spreads traffic.

## A chassis, or many fixed switches

Large operators have published why they moved away from big boxes. Facebook's network team wrote in 2014 that its earlier clusters hung "hundreds of server cabinets" on "a set of large, high-radix cluster switches", already in "a reliable layer3 'four-post' architecture, offering 3+1 cluster switch redundancy", and that bigger boxes were not better operationally: "With large areas of the datacenter depending on just a few boxes, the impact of hardware and software failures can also be significant" ([Alexey Andreyev, Facebook Engineering, Introducing data center fabric, the next-generation Facebook data center network, 14 November 2014](https://engineering.fb.com/2014/11/14/production-engineering/introducing-data-center-fabric-the-next-generation-facebook-data-center-network/)). The fabric that replaced them used pods of "only 48 server racks", each served by "a set of four devices that we call fabric switches", with "4 x 40G uplinks" from each top-of-rack switch, and "four independent 'planes' of spine switches, each scalable up to 48 independent devices within a plane" (Andreyev, as above). Worked from those numbers: a rack has 4 × 40 = 160 Gb/s of uplink, and the loss of one of its four fabric switches leaves 3 × 40 = 120 Gb/s, 75 percent of capacity rather than an outage.

Google's account of its data centre networks makes the same argument in general form. Its Clos topologies "have substantial in-built path diversity and redundancy, so the failure of any individual element can result in relatively small capacity reduction", and the size of a cluster matters because "Power is distributed hierarchically at the granularity of the building, multi-Megawatt power generators, and physical datacenter rows. Each level of hierarchy represents a unit of failure and maintenance", so "Running storage across a cluster requires both rack and power diversity to avoid correlated failures" ([Singh and others, Jupiter Rising: A Decade of Clos Topologies and Centralized Control in Google's Datacenter Network, ACM SIGCOMM 2015](https://conferences.sigcomm.org/sigcomm/2015/pdf/papers/p183.pdf)). The power hierarchy and the network hierarchy have to be read together: a pair of switches in the same row on the same power distribution is one failure domain, however the cables run.

| Design | What one failure costs | What one software defect or change can reach | How maintenance is done |
|---|---|---|---|
| Chassis with two supervisors | A supervisor: a switchover, subsecond on the Catalyst 9400; a line card: its ports | The whole chassis runs one software image | ISSU, or a window |
| Two fixed switches as a pair (MLAG, stack) | One switch: the pair runs on the survivor | One switch, or both in a stack with one control plane | One switch at a time, for MLAG |
| Many fixed switches in a Clos fabric | One fabric switch: a fraction of capacity, 25 percent of a pod's uplinks in Facebook's four-plane design | One device, if changes are rolled out gradually | Drain a device, change it, restore it |

Which of these a network needs depends on its size and its team, and the sources above describe trade-offs rather than a winner. What none of them changes is the layer below: two chassis or forty fixed switches on one power feed, in one row, behind one trench, share that feed, that row and that trench. The [change blast-radius mapper](https://ronutz.com/en/tools/change-blast-radius-mapper) puts those shared things on paper before a change, and [hidden assumptions in an architecture diagram](https://ronutz.com/en/learn/hidden-assumptions-in-an-architecture-diagram) lists where they hide; [reviewing a network architecture before approving it](https://ronutz.com/en/learn/review-a-network-architecture-before-approving-it) turns the same questions into a review.

## How these failures are found

Physical shared fate does not show up in a routing table. It is found by walking the things the diagrams leave out, and the reports above show which walks matter; when the failure is already happening, [the first hour of fault isolation](https://ronutz.com/en/learn/fault-isolation-first-hour) is the method.

- **Trace each feed** from the power supply to the panel, the distribution unit and the UPS, and check that the A and B supplies of every dual-corded device land on different feeds; then pull one feed in a window and watch, as AWS's full load test did for its generators (AWS, as above).
- **Test the generator under real load,** not only at start: the FCC found that a UPS problem kept one office's generators from being load tested "under actual site load" for months before the derecho (FCC, derecho report, as above).
- **Ask for route maps and SRLG identifiers** from each carrier, compare them, and repeat after every circuit move, as the FCC requires for emergency service (47 CFR 9.19, as above).
- **Run the out-of-band network on its own power and its own provider,** and use it routinely, so that it is known to work before the day it is the only way in (Xona Partners, as above).
- **Read the facility's documents for topology, not percentages:** a tier or rating says what can be maintained or lost without shutdown; a percentage, by the Uptime Institute's own account, does not follow from it (Lawrence, as above).
- **Write the incident down with times,** so that the next design starts from what happened; the [incident timeline builder](https://ronutz.com/en/tools/incident-timeline-rca-builder) structures it, and [what belongs in a post-incident review](https://ronutz.com/en/learn/what-belongs-in-a-post-incident-technical-review) says what to keep. Drills that pull a feed or a carrier on purpose are the subject of [part 10](https://ronutz.com/en/learn/testing-redundancy-failure-drills-chaos-and-the-failover-never-tried).

## What to remember

- N+1 power protects against a failed supply; N+N with the supplies split across independent circuits protects against a failed feed. Two supplies on one feed are one supply.
- The chain behind the socket breaks at the handover: generators that do not stabilize (AWS 2012), generators that must run in tandem (Arlington 2012), cooling that trips with the power (Azure 2023), a UPS room that floods (Paris 2023). Batteries buy minutes or hours, not days.
- The Uptime Institute's tiers describe topology, from shutdown-for-maintenance (I) to fault tolerant (IV), and the institute says there is no direct relationship between a tier and a number of nines; TIA-942 rates four levels, revision C of 2024.
- Paths are diverse only if they share no segment, cable or circuit board (the FCC's test); a shared risk link group names what they share; most long-haul conduits in the United States carry two or more major providers.
- Two carriers are not two paths until their routes are shown to be separate, and diversity decays as circuits are rearranged; audit it.
- Out-of-band management must not depend on the data network, its power or its provider (CRTC on Rogers, Meta, Halamka).
- Redundant supervisors switch over in about a second or less but keep the control plane only with graceful restart or nonstop routing; many fixed switches turn a box failure into a capacity loss, at the cost of more devices to run.

<ReaderQuestions>

- If a facility is certified Tier III and its operator also quotes 99.98 percent, which of the two would you put in a contract, and how would you measure it?
- Your two carriers both say their circuits are diverse: what evidence would convince you, and who should check it again after the next rearrangement?
- The FCC requires 24 or 72 hours of backup power for some emergency-call offices; how many hours would you require for your own core sites, and what would you do at hour 25?
- Azure's halls had seven chillers for a need of four and still overheated: when does a spare that has to be restarted by hand count as redundancy?
- Brazilian regulation refunds users for interruptions but does not require diverse paths; should it, for which services, and who would pay?

</ReaderQuestions>

## Sources

- [Juniper Networks, Junos OS High Availability User Guide, published 15 November 2026: N+1 and N+N power supply redundancy and its table, redundant power, NSSU and LAG members on different line cards (accessed 16 November 2026)](https://www.juniper.net/documentation/us/en/software/junos/high-availability/high-availability.pdf)
- [Cisco, Catalyst 9400 Series switches data sheet, updated 1 September 2026: N+1 and N+N with independent input circuits, power supply bays, 1+1 supervisor redundancy, N+1 fans, ISSU under 200 ms (accessed 16 November 2026)](https://www.cisco.com/c/en/us/products/collateral/switches/catalyst-9400-series-switches/nb-06-cat9400-ser-data-sheet-cte-en.html)
- [Amazon Web Services, Summary of the AWS Service Event in the US East Region, 2 July 2012: voltage spike, generators that failed to stabilize, UPS depletion at 8:04 pm, testing history and changes (accessed 16 November 2026)](https://aws.amazon.com/message/67457/)
- [Federal Communications Commission, Public Safety and Homeland Security Bureau, Impact of the June 2012 Derecho on Communications Networks and Services, Report and Recommendations, January 2013: backup power failures, 9 of 136 generators, tandem generators and CSRIC 8-7-5281, six hours on batteries, thirty-minute monitoring UPS, diversity audits and CSRIC 8-7-0532 (accessed 16 November 2026)](https://docs.fcc.gov/public/attachments/DOC-318331A1.pdf)
- [Google Cloud, Google Compute Engine Persistent Disk issue in europe-west1-b, incident 15056, 13 to 17 August 2015: four lightning strikes, battery drain, data loss under 0.000001 percent (accessed 16 November 2026)](https://status.cloud.google.com/incident/compute/15056)
- [Microsoft Azure, Post Incident Review, Services impacted after power/cooling issue, Australia East, 30 August 2023, tracking ID VVTQ-J98: voltage sag, 13 chillers, seven installed for four needed, thermal runaway (accessed 16 November 2026)](https://azure.status.microsoft/en-us/status/history/?trackingid=VVTQ-J98)
- [Google Cloud, Multiple Google Cloud services in the europe-west9-a zone are impacted, Paris, 25 April 2023: water leak into the UPS room, fire, building power shutdown, quorum not distributed across three buildings (accessed 16 November 2026)](https://status.cloud.google.com/incidents/dS9ps52MUnxQfyDGPfkY)
- [Uptime Institute, Uptime Announces Annual Outage Analysis Report 2025, press release, 6 May 2025: power the leading cause of impactful outages, IT and networking 23 percent, data basis (accessed 16 November 2026)](https://www.businesswire.com/news/home/20250506733553/en/Uptime-Announces-Annual-Outage-Analysis-Report-2025)
- [United States, Code of Federal Regulations, title 47, part 9, section 9.19, Provision of reliable 911 service, eCFR current text: physical diversity defined, diversity audits and tagging, 24 and 72 hours of backup power (accessed 16 November 2026)](https://www.ecfr.gov/api/renderer/v1/content/enhanced/current/title-47?part=9&section=9.19)
- [Uptime Institute, Tier Classification System: Tier I to IV, over 4,300 certifications in more than 120 countries (accessed 16 November 2026)](https://uptimeinstitute.com/tiers)
- [Andy Lawrence, Uptime Institute Journal, 99 Red Flags: The Availability Nines, 28 October 2019: no direct relationship between nines and tiers, expected figures no longer relevant (accessed 16 November 2026)](https://journal.uptimeinstitute.com/?p=6064)
- [B3, Política Comercial de Serviços de Co-location, version 3.5, 15 January 2024: Tier III certificate from the Uptime Institute, 99.98 percent statement (accessed 16 November 2026)](https://sistemasweb.b3.com.br/normativos/POLITICA%20COMERCIAL%20COLOCATION%20-%20PORTUGUES.PDF)
- [TIA, TIA Unveils Revision C of the Global Data Center Infrastructure Standard, 9 May 2024 (accessed 16 November 2026)](https://tiaonline.org/news/tia-unveils-revision-c-of-the-global-data-center-infrastructure-standard/)
- [TIA, TIA Advances AI Ready Data Centers with New ANSI/TIA 942 Addendum, Global Certification Leadership, and Expanded Industry Quality Initiative, 24 March 2026: four rated levels of reliability, Addendum 1 (artificial intelligence) to ANSI/TIA-942-C targeted for mid-2027 (accessed 16 November 2026)](https://tiaonline.org/news/tia-advances-ai-ready-data-centers-with-new-ansi-tia-942-addendum-global-certification-leadership-and-expanded-industry-quality-initiative/)
- [RFC 4202, Routing Extensions in Support of Generalized Multi-Protocol Label Switching (GMPLS), October 2005, Proposed Standard: section 2.3, shared risk link groups (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc4202.txt)
- [RFC 3386, Network Hierarchy and Multilayer Survivability, November 2002, Informational: shared risk groups (accessed 16 November 2026)](https://www.rfc-editor.org/rfc/rfc3386.txt)
- [Ramakrishnan Durairajan, Paul Barford, Joel Sommers and Walter Willinger, InterTubes: A Study of the US Long-haul Fiber-optic Infrastructure, ACM SIGCOMM 2015, 17 to 21 August 2015: 542 conduits, shares by two, three and four providers, 12 conduits with more than 17 (accessed 16 November 2026)](https://pages.cs.wisc.edu/~pb/tubes_final.pdf)
- [B3, Manual de Acesso à Infraestrutura Tecnológica, version 8.5, 13 February 2026: two distinct providers with distinct physical routes, access forms, first-hop redundancy (accessed 16 November 2026)](https://b3.com.br/data/files/B9/F0/1F/4F/DC7CF91094DCD8F9AC094EA8/2026%20-%20Manual%20de%20Acesso%20a%20Infraestrutura%20Tecnologica%20da%20B3.pdf)
- [Anatel, Resolução nº 777, de 28 de abril de 2025, Regulamento Geral dos Serviços de Telecomunicações (RGST): article 5, continuity in the public and private regimes (accessed 16 November 2026)](https://informacoes.anatel.gov.br/legislacao/resolucoes/2025/2022-resolucao-777)
- [Anatel, Resolução nº 717, de 23 de dezembro de 2019, Regulamento de Qualidade dos Serviços de Telecomunicações (RQUAL): interruption and massive interruption, 24-hour notice, proportional refunds (accessed 16 November 2026)](https://informacoes.anatel.gov.br/legislacao/resolucoes/2019/1371-resolucao-717)
- [Anatel, Resolução nº 740, de 21 de dezembro de 2020, Regulamento de Segurança Cibernética Aplicada ao Setor de Telecomunicações (R-Ciber): critical infrastructures, the principle of diversity (accessed 16 November 2026)](https://informacoes.anatel.gov.br/legislacao/resolucoes/2020/1497-resolucao-740)
- [John Halamka, The CareGroup Network Outage, Life as a Healthcare CIO, 4 March 2008: out-of-band tools (accessed 16 November 2026)](https://geekdoctor.blogspot.com/2008/03/caregroup-network-outage.html)
- [Santosh Janardhan, Meta Engineering, More details about the October 4 outage, 5 October 2021: primary and out-of-band access down, engineers on site (accessed 16 November 2026)](https://engineering.fb.com/2021/10/05/networking-traffic/outage-details/)
- [Xona Partners for the Canadian Radio-television and Telecommunications Commission, Assessment of Rogers Networks for Resiliency and Reliability Following the 8 July 2022 Outage, Executive Summary, July 2024: duration, 12 million customers, management network on the IP core, separation recommendations (accessed 16 November 2026)](https://crtc.gc.ca/eng/publications/reports/xona2024.htm)
- [Juniper Networks, understanding graceful Routing Engine switchover: 2-second keepalive, forwarding not interrupted, control plane not preserved without graceful restart or NSR (accessed 16 November 2026)](https://www.juniper.net/documentation/us/en/software/junos/high-availability/topics/concept/gres-overview.html)
- [Alexey Andreyev, Facebook Engineering, Introducing data center fabric, the next-generation Facebook data center network, 14 November 2014: cluster switches, 3+1 redundancy, pods of 48 racks, four fabric switches, four spine planes (accessed 16 November 2026)](https://engineering.fb.com/2014/11/14/production-engineering/introducing-data-center-fabric-the-next-generation-facebook-data-center-network/)
- [Arjun Singh and others, Jupiter Rising: A Decade of Clos Topologies and Centralized Control in Google's Datacenter Network, ACM SIGCOMM 2015: path diversity, power hierarchy as failure units, rack and power diversity (accessed 16 November 2026)](https://conferences.sigcomm.org/sigcomm/2015/pdf/papers/p183.pdf)